Step 1. Locate the motor name plate
NOTE
The motor is either star- (Y) or delta- connected (Δ). This
information is located on the motor name plate data.
3~ MOTOR NR. 1827421 2003
S/E005A9
1,5 KW
n 31,5 /min. 400 Y V
n 1400 /min. 50 Hz
COS 0,80 3,6 A
1,7L
B IP 65 H1/1A
BAUER D-7 3734 ESLINGEN
130BT307.10
Illustration 7.69 Motor Name plate
Step 2. Enter the motor name plate data in this parameter
list.
To access this list, first press [Quick Menu] then select “Q2
Quick Setup”.
1.
1-20 Motor Power [kW]
1-21 Motor Power [HP]
2.
1-22 Motor Voltage
3.
1-23 Motor Frequency
4.
1-24 Motor Current
5.
1-25 Motor Nominal Speed
Step 3. Select OGD motor data
1.
Set 1-11 Motor Model to 'Danfoss OGD LA10'.
Step 4. Set speed limit and ramp times
Set up the desired limits for speed and ramp time:
3-02 Minimum Reference
3-03 Maximum Reference
4-11 Motor Speed Low Limit [RPM] or 4-12 Motor
Speed Low Limit [Hz]
4-13 Motor Speed High Limit [RPM] or 4-14 Motor
Speed High Limit [Hz]
3-41 Ramp 1 Ramp Up Time
3-42 Ramp 1 Ramp Down Time
Electrical Installation
VLT
®
AutomationDrive FC 300 Design Guide, 0.25-75 kW
148 MG33BE02 - VLT
®