NOTE
In motors without phase insulation paper or other
insulation reinforcement suitable for operation with
voltage supply (such as a frequency converter), fit a Sine-
wave filter on the output of the frequency converter.
Cable entry holes
The suggested use of the holes are purely recommen-
dations and other solutions are possible. Unused cable
entry holes can be sealed with rubber grommets (for IP21).
* Tolerance ± 0.2 mm
[4]
[5]
[1]
[3]
[2]
130BB656.10
Illustration 7.22 A2 - IP21
Hole Number and recommended
use
Dimensions
1)
Nearest metric
UL [in] [mm]
1) Mains 3/4 28.4 M25
2) Motor 3/4 28.4 M25
3) Brake/Load S 3/4 28.4 M25
4) Control Cable 1/2 22.5 M20
5) Control Cable 1/2 22.5 M20
Table 7.3 Legend to Illustration 7.22
1)
Tolerance
±
0.2 mm
[4]
[5]
[6]
[1]
[3]
[2]
130BB657.10
Illustration 7.23 A3 - IP21
Hole Number and recommended
use
Dimensions
1)
Nearest metric
UL [in] [mm]
1) Mains 3/4 28.4 M25
2) Motor 3/4 28.4 M25
3) Brake/Load Sharing 3/4 28.4 M25
4) Control Cable 1/2 22.5 M20
5) Control Cable 1/2 22.5 M20
6) Control Cable 1/2 22.5 M20
Table 7.4 Legend to Illustration 7.23
1)
Tolerance
±
0.2 mm
[5]
[3]
[2]
[4]
[1]
130BB663.10
Illustration 7.24 A4 - IP55
Hole Number
and
recommended
use
Dimensions
1)
Nearest metric
UL [in] [mm]
1) Mains 3/4 28.4 M25
2) Motor 3/4 28.4 M25
3) Brake/Load
Sharing
3/4 28.4 M25
4) Control
Cable
1/2 22.5 M20
5) Removed - - -
Table 7.5 Legend to Illustration 7.24
1)
Tolerance
±
0.2 mm
[4]
[2]
[3]
[5]
[1]
130BB665.10
Illustration 7.25 A4 - IP55 Threaded Gland Holes
Hole Number and recommended use Dimensions
1) Mains M25
2) Motor M25
3) Brake/Load Sharing M25
4) Control Cable M16
5) Control Cable M20
Table 7.6 Legend to Illustration 7.25
Electrical Installation
VLT
®
AutomationDrive FC 300 Design Guide, 0.25-75 kW
118 MG33BE02 - VLT
®
is a registered Danfoss trademark
77