Enclosure
size
Power [kW] Recommended
fuse size
Recommended
Max. fuse
Recommended circuit
breaker Moeller
Max trip level [A]
A1 0.37-1.5 gG-10 gG-25 PKZM0-16 16
A2 0.37-4.0 gG-10 (0.37-3)
gG-16 (4)
gG-25 PKZM0-25 25
A3 5.5-7.5 gG-16 gG-32 PKZM0-25 25
B3 11-15 gG-40 gG-63 PKZM4-50 50
B4 18.5-30 gG-50 (18.5)
gG-63 (22)
gG-80 (30)
gG-125 NZMB1-A100 100
C3 37-45 gG-100 (37)
gG-160 (45)
gG-150 (37)
gG-160 (45)
NZMB2-A200 150
C4 55-75 aR-200 (55)
aR-250 (75)
aR-250 NZMB2-A250 250
A4 0.37-4 gG-10 (0.37-3)
gG-16 (4)
gG-32 PKZM0-25 25
A5 0.37-7.5 gG-10 (0.37-3)
gG-16 (4-7.5)
gG-32 PKZM0-25 25
B1 11-15 gG-40 gG-80 PKZM4-63 63
B2 18.5-22 gG-50 (18.5)
gG-63 (22)
gG-100 NZMB1-A100 100
C1 30-45 gG-80 (30)
gG-100 (37)
gG-160 (45)
gG-160 NZMB2-A200 160
C2 55-75 aR-200 (55)
aR-250 (75)
aR-250 NZMB2-A250 250
Table 7.20 380-500 V, Frame Sizes A, B and C
Electrical Installation
VLT
®
AutomationDrive FC 300 Design Guide, 0.25-75 kW
124 MG33BE02 - VLT
®
is a registered Danfoss trademark