EasyManua.ls Logo

Danfoss VLT AutomationDrive FC 300 Series - Page 154

Danfoss VLT AutomationDrive FC 300 Series
204 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
S t a r t ( 1 8 )
F r e e z e r e f ( 2 7 )
S p e e d u p ( 2 9 )
S p e e d d o w n ( 3 2 )
S p e e d
R e f e r e n c e
130BB840.10
Illustration 8.3 Speed Up/Down
Parameters
FC
+24 V
+24 V
D IN
D IN
D IN
COM
D IN
D IN
D IN
D IN
+10
V
A IN
A IN
COM
A OUT
COM
R1R2
12
13
18
19
20
27
29
32
33
37
50
53
54
55
42
39
01
02
03
04
05
06
-
61
68
69
RS-485
+
130BB685.10
Function Setting
8-30 Protocol FC*
8-31 Address 1*
8-32 Baud Rate 9600*
*=Default Value
Notes/comments:
Select protocol, address and
baud rate in the above
mentioned parameters.
Table 8.11 RS-485 Network Connection
Parameters
FC
+24 V
+24 V
D IN
D IN
D IN
COM
D IN
D IN
D IN
D IN
+10
V
A IN
A IN
COM
A OUT
COM
12
13
18
19
20
27
29
32
33
37
50
53
54
55
42
39
A53
U - I
130BB686.11
Function Setting
1-90 Motor
Thermal
Protection
[2]
Thermistor
trip
1-93 Thermistor
Source
[1] Analog
input 53
*=Default Value
Notes/comments:
If only a warning is desired,
1-90 Motor Thermal Protection
should be set to [1] Thermistor
warning.
Table 8.12 Motor Thermistor
Application Examples
VLT
®
AutomationDrive FC 300 Design Guide, 0.25-75 kW
152 MG33BE02 - VLT
®
is a registered Danfoss trademark
88
RSPSupply - 1-888-532-2706 - www.RSPSupply.com
http://www.RSPSupply.com/p-21462-Danfoss-131B8966-VLT-Automation-VT-Drive-VFD-FC301-230V-5-HP.aspx

Table of Contents

Other manuals for Danfoss VLT AutomationDrive FC 300 Series

Related product manuals