P5K5 P7K5 P11K
High/Normal Load
1)
HO NO HO NO HO NO
Typical Shaft Output [kW] 5.5 7.5 7.5 11 11 15
Enclosure IP20 B3 B3 B4
Enclosure IP21 B1 B1 B2
Enclosure IP55, IP66 B1 B1 B2
Output current
Continuous (3x200-240 V) [A] 24.2 30.8 30.8 46.2 46.2 59.4
Intermittent (60 s overload)
(3x200-240 V) [A]
38.7 33.9 49.3 50.8 73.9 65.3
Continuous kVA (208 V AC) [kVA] 8.7 11.1 11.1 16.6 16.6 21.4
Max. input current
Continuous (3x200-240 V) [A] 22 28 28 42 42 54
Intermittent (60 s overload)
(3x200-240 V) [A]
35.2 30.8 44.8 46.2 67.2 59.4
Additional specifications
IP21 max. cable cross-section
5)
(mains, brake,
load sharing) [mm
2
(AWG)]
2)
16,10, 16 (6,8,6) 16,10, 16 (6,8,6) 35,-,- (2,-,-)
IP21 max. cable cross-section
5)
(motor) [mm
2
(AWG)]
2)
10,10,- (8,8,-) 10,10,- (8,8,-) 35,25,25 (2,4,4)
IP20 max. cable cross-section
5)
(mains, brake,
motor and load sharing)
10,10,- (8,8,-) 10,10,- (8,8,-) 35,-,- (2,-,-)
Max. cable cross-section with Disconnect [mm
2
(AWG)]
2)
16,10,10 (6,8,8)
Estimated power loss
at rated max. load [W]
4)
239 310 371 514 463 602
Weight,
enclosure IP21, IP55, IP66 [kg]
23 23 27
Efficiency
4)
0.964 0.959 0.964
Table 4.2 Mains Supply 3x200-240 V AC
FC 300 Selection
VLT
®
AutomationDrive FC 300 Design Guide, 0.25-75 kW
60 MG33BE02 - VLT
®
is a registered Danfoss trademark
44
RSPSupply - 1-888-532-2706 - www.RSPSupply.com
http://www.RSPSupply.com/p-21462-Danfoss-131B8966-VLT-Automation-VT-Drive-VFD-FC301-230V-5-HP.aspx

Table of Contents

Other manuals for Danfoss VLT AutomationDrive FC 300 Series

Related product manuals