Loading...
Cable
length [m]
Mains
voltage
[V]
Rise time
[μs]
Upeak
[kV]
du/dt
[kV/μs]
30 240 0.300 0.598 1.594
100 240 0.536 0.566 0.844
150 240 0.776 0.546 0.562
Table 4.20 P30KT2
Cable
length [m]
Mains
voltage
[V]
Rise time
[μs]
Upeak
[kV]
du/dt
[kV/μs]
30 240 0.300 0.598 1.594
100 240 0.536 0.566 0.844
150 240 0.776 0.546 0.562
Table 4.21 P37KT2
Cable
length [m]
Mains
voltage
[V]
Rise time
[μs]
Upeak
[kV]
du/dt
[kV/μs]
5 480 0.640 0.690 0.862
50 480 0.470 0.985 0.985
150 480 0.760 1.045 0.947
Table 4.22 P1K5T4
Cable
length [m]
Mains
voltage
[V]
Rise time
[μs]
Upeak
[kV]
du/dt
[kV/μs]
5 480 0.172 0.890 4.156
50 480 0.310 2.564
150 480 0.370 1.190 1.770
Table 4.23 P4K0T4
Cable
length [m]
Mains
voltage
[V]
Rise time
[μs]
Upeak
[kV]
du/dt
[kV/μs]
5 480 0.04755 0.739 8.035
50 480 0.207 4.548
150 480 0.6742 1.030 2.828
Table 4.24 P7K5T4
Cable
length [m]
Mains
voltage
[V]
Rise time
[μs]
Upeak
[kV]
du/dt
[kV/μs]
36 480 0.396 1.210 2.444
100 480 0.844 1.230 1.165
150 480 0.696 1.160 1.333
Table 4.25 P11KT4
Cable
length [m]
Mains
voltage
[V]
Rise time
[μs]
Upeak
[kV]
du/dt
[kV/μs]
36 480 0.396 1.210 2.444
100 480 0.844 1.230 1.165
150 480 0.696 1.160 1.333
Table 4.26 P15KT4
Cable
length [m]
Mains
voltage
[V]
Rise time
[μs]
Upeak
[kV]
du/dt
[kV/μs]
36 480 0.312 2.846
100 480 0.556 1.250 1.798
150 480 0.608 1.230 1.618
Table 4.27 P18KT4
Cable
length [m]
Mains
voltage
[V]
Rise time
[μs]
Upeak
[kV]
du/dt
[kV/μs]
15 480 0.288 3.083
100 480 0.492 1.230 2.000
150 480 0.468 1.190 2.034
Table 4.28 P22KT4
Cable
length [m]
Mains
voltage
Rise time
[μs]
Upeak
[kV]
du/dt
[kV/μs]
5 480 0.368 1.270 2.853
50 480 0.536 1.260 1.978
100 480 0.680 1.240 1.426
150 480 0.712 1.200 1.334
Table 4.29 P30KT4
Cable
length [m]
Mains
voltage
[V]
Rise time
[μs]
Upeak
[kV]
du/dt
[kV/μs]
5 480 0.368 1.270 2.853
50 480 0.536 1.260 1.978
100 480 0.680 1.240 1.426
150 480 0.712 1.200 1.334
Table 4.30 P37KT4
Cable
length [m]
Mains
voltage
[V]
Rise time
[μs]
Upeak
[kV]
du/dt
[kV/μs]
15 480 0.256 1.230 3.847
50 480 0.328 1.200 2.957
100 480 0.456 1.200 2.127
150 480 0.960 1.150 1.052
Table 4.31 P45KT4
FC 300 Selection
VLT
®
AutomationDrive FC 300 Design Guide, 0.25-75 kW
MG33BE02 - VLT
®
is a registered Danfoss trademark 77
4 4
RSPSupply - 1-888-532-2706 - www.RSPSupply.com
http://www.RSPSupply.com/p-21462-Danfoss-131B8966-VLT-Automation-VT-Drive-VFD-FC301-230V-5-HP.aspx

Table of Contents

Other manuals for Danfoss VLT AutomationDrive FC 300 Series

Related product manuals