8-34 Estimated cycle time
Range: Function:
0 ms* [0 - 1000000 ms] In a noisy environments, the interface may be blocked by due to overload of bad frames. This
parameter specifies the time between two consecutive frames on the network. If the interface does
not detect valid frames in that time it flushes the receive buffer.
8-35 Minimum Response Delay
Range: Function:
10 ms* [Application dependant] Specify the minimum delay time between receiving a request and transmitting a response. This is
used for overcoming modem turnaround delays.
8-36 Max Response Delay
Range: Function:
Application
dependent*
[Application dependant] Specify the maximum permissible delay time between transmitting a request and receiving a re-
sponse. Exceeding this delay time will cause control word time-out.
8-37 Max Inter-Char Delay
Range: Function:
Application
dependent*
[Application dependant] Specify the maximum permissible time interval between receipt of two bytes. This parameter acti-
vates time-out if transmission is interrupted.
This parameter is active only when par. 8-30
Protocol
is set to
FC MC
[1] protocol.
3.10.5 8-4* FC MC protocol set
8-40 Telegram selection
Option: Function:
[1] * Standard telegram 1 Enables use of freely configurable telegrams or standard telegrams for the FC port.
[100] None
[101] PPO 1
[102] PPO 2
[103] PPO 3
[104] PPO 4
[105] PPO 5
[106] PPO 6
[107] PPO 7
[108] PPO 8
[200] Custom telegram 1 Enables use of freely configurable telegrams or standard telegrams for the FC port.
[202] Custom telegram 3
8-41 Parameters for signals
Option: Function:
[0] * None This parameter contains a list of signals available for selection in par. 8-42
PCD write configura-
tion
and par. 8-43
PCD read configuration
.
[302] Minimum Reference
[303] Maximum Reference
[312] Catch up/slow Down Value
[341] Ramp 1 Ramp up Time
[342] Ramp 1 Ramp Down Time
[351] Ramp 2 Ramp up Time
3 Parameter descriptions FC 300 Programming Guide
140
MG.33.M8.02 - VLT
®
is a registered Danfoss trademark
3

Other manuals for Danfoss VLT AutomationDrive FC 300

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AutomationDrive FC 300 and is the answer not in the manual?

Danfoss VLT AutomationDrive FC 300 Specifications

General IconGeneral
BrandDanfoss
ModelVLT AutomationDrive FC 300
CategoryDC Drives
LanguageEnglish

Related product manuals