8-54 Reversing Select
Option: Function:
[0] Digital input Select control of the frequency converter reverse function via the terminals (digital input) and/or
via the fieldbus.
[1] Bus Activates the Reverse command via the serial communication port or fieldbus option.
[2] Logic AND Activates the Reverse command via the fieldbus/serial communication port, AND additionally via
one of the digital inputs.
[3] * Logic OR Activates the Reverse command via the fieldbus/serial communication port OR via one of the digital
inputs.
NB!
This parameter is only active when par. 8-01
Control Site
is set to [0]
Digital and control word
.
8-55 Set-up Select
Option: Function:
Select control of the frequency converter set-up selection via the terminals (digital input) and/or via
the fieldbus.
[0] Digital input Activates the set-up selection via a digital input.
[1] Bus Activates the set-up selection via the serial communication port or fieldbus option.
[2] Logic AND Activates the set-up selection via the fieldbus/serial communication port, AND additionally via one
of the digital inputs.
[3] * Logic OR Activate the set-up selection via the fieldbus/serial communication port OR via one of the digital
inputs.
NB!
This parameter is active only when par. 8-01
Control Site
is set to [0]
Digital and control word
.
8-56 Preset Reference Select
Option: Function:
Select control of the frequency converter Preset Reference selection via the terminals (digital input)
and/or via the fieldbus.
[0] Digital input Activates Preset Reference selection via a digital input.
[1] Bus Activates Preset Reference selection via the serial communication port or fieldbus option.
[2] Logic AND Activates Preset Reference selection via the fieldbus/serial communication port, AND additionally
via one of the digital inputs.
[3] * Logic OR Activates the Preset Reference selection via the fieldbus/serial communication port OR via one of
the digital inputs.
NB!
This parameter is active only when par. 8-01
Control Site
is set to [0]
Digital and control word
.
3 Parameter descriptions FC 300 Programming Guide
148
MG.33.M8.02 - VLT
®
is a registered Danfoss trademark