8-57 Profidrive OFF2 Select
Select control of the drive OFF2 selection via the terminals (digital input) and/or via the fieldbus. This parameter is active only when par. 8-01 Control
Site is set to [0] Digital and ctrl. word and par. 8-10 is set to [1] Profidrive profile.
Option: Function:
[0] Digital input
[1] Bus
[2] Logic AND
[3] * Logic OR
8-58 Profidrive OFF3 Select
Select control of the drive OFF3 selection via the terminals (digital input) and/or via the fieldbus. This parameter is active only when par. 8-01 Control
Site is set to [0] Digital and control word and par. 8-10 is set to [1] Profidrive profile.
Option: Function:
[0] Digital input
[1] Bus
[2] Logic AND
[3] * Logic OR
3.10.7 8-8* FC Port Diagnostics
These parameters are used for monitoring the Bus communication via the FC Port.
8-80 Bus Message Count
Range: Function:
0 N/A* [0 - 0 N/A] This parameter shows the number of valid telegrams detected on the bus.
8-81 Bus Error Count
Range: Function:
0 N/A* [0 - 0 N/A] This parameter shows the number of telegrams with faults (e.g. CRC fault), detected on the bus.
8-82 Slave Messages Rcvd
Range: Function:
0 N/A* [0 - 0 N/A] This parameter shows the number of valid telegrams addressed to the slave, sent by the frequency
converter.
8-83 Slave Error Count
Range: Function:
0 N/A* [0 - 0 N/A] This parameter shows the number of error telegrams, which could not be executed by the frequency
converter.
3.10.8 8-9* Bus Jog
Parameters for configuring the Bus Jog.
8-90 Bus Jog 1 Speed
Range: Function:
100 RPM* [Application dependant] Enter the jog speed. This is a fixed jog speed activated via the serial port or fieldbus option.
8-91 Bus Jog 2 Speed
Range: Function:
200 RPM* [Application dependant] Enter the jog speed. This is a fixed jog speed activated via the serial port or fieldbus option.
FC 300 Programming Guide 3 Parameter descriptions