12-21 Process Data Config Write
Range: Function:
[[0 - 9] PCD read 0 - 9] Configuration of readable process data.
NB!
For configuration of 2-word (32-bit) parameter read/write, use 2 consecutive arrays in par. 12-21 and 12-22.
12-22 Process Data Config Read
Range: Function:
[[0 - 9] PCD read 0 - 9] Configuration of readable process data.
12-28 Store Data Values
Option: Function:
This parameter activates a function that stores all parameter values in the non-volatile memory
(EEPROM) thus retaining parameter values at power-down.
The parameter returns to “Off”.
[0] * Off The store function is inactive.
[1] Store All set-ups All parameter value will be stored in the non-volatile memory, in all four setups.
12-29 Store Always
Option: Function:
Activates function that will always store received parameter data in non-volatile memory (EEPROM).
[0] * Off
[1] On
3.13.4 12-3* EtherNet/IP
12-30 Warning Parameter
Range: Function:
[0000 – FFFF hex] Read only. Displays the EtherNet/IP specific 16-bit Status-word.
Bit Description
0 Owned
1Not used
2 Configured
3Not used
4 Not used
5Not used
6 Not used
7Not used
8 Minor recoverable fault
9 Minor unrecoverable fault
10 Major recoverable fault
11 Major unrecoverable fault
12 Not used
13 Not used
14 Not used
15 Not used
FC 300 Programming Guide 3 Parameter descriptions
MG.33.M8.02 - VLT
®
is a registered Danfoss trademark
171
3