14-53 Fan Monitor
Option: Function:
Select which reaction the frequency converter should take in case a fan fault is detected.
[0] Disabled
[1] * Warning
[2] Trip
14-55 Output Filter
Option: Function:
Select the type of output filter connected. This parameter cannot be adjusted while motor is running.
[0] * No Filter
[1] Sine-Wave Filter
[2] Sine-Wave Filter Fixed
14-56 Capacitance Output Filter
Compensation function of the LC-filter requires the per phase equivalent star connected capacitance of the filter (3 times the capacity between two
phases when capacitance is ’Delta’ connection).
Range: Function:
2.0 uF* [0.1 - 6500.0 uF] Set the capacitance of the output filter. The value can be found on the filter label.
NB!
This is required for correct compensation in Flux mode (par. 1-01
Motor Control
Principle
)
14-57 Inductance Output Filter
Range: Function:
7.000 mH* [0.001 - 65.000 mH] Set the inductance of the output filter. The value can be found on the filter label.
NB!
This is required for correct compensation in Flux mode (par. 1-01
Motor Control
Principle
)
3.15.8 14-7* Compatibility
The parameters in this group are for setting of compatibility for VLT 3000, VLT 5000 to FC 300
14-72 VLT Alarm Word
Option: Function:
[0] 0 - 4294967295 Read out the alarm word corresponding to VLT 5000
14-73 VLT Warning Word
Option: Function:
[0] 0 - 4294967295 Read out the warning word corresponding to VLT 5000
14-74 VLT Ext. Status Word
Range: Function:
0* [0 - 4294967295 ] Read out the ext. status word corresponding to VLT 5000
FC 300 Programming Guide 3 Parameter descriptions