3.15.9 14-8* Options
14-80 Option Supplied by External 24VDC
Option: Function:
[0] No Select No [0] to use the drive's 24 V DC supply.
[1] * Yes Select Yes [1] if an external 24 V DC supply will be used to power the option. Inputs/Outputs will
be galvanically isolated from the drive when operated from an external supply.
NB!
This parameter is only changing function by performing a power cycle.
14-90 Fault Level
Option: Function:
[0] * Off Use this parameter to customize Fault levels. Use [0] "Off" with caution as it will ignore all Warnings
& Alarms for the chosen source.
[1] Warning
[2] Trip
[3] Trip Lock
Failure Alarm Off Warning Trip Trip Lock
10V low 1 X X *
24V low 47 X X*
1.8V supply low 48 X X*
Voltage limit 64 X X*
Earth fault during ramping 14 X* X
Earth fault 2 during cont. operation 45 X* X
Torque Limit 12 X X*
Table 3.4: Table for selection of choice of action when selected alarm appear:
3 Parameter descriptions FC 300 Programming Guide
204