EasyManuals Logo
Home>Danfoss>DC Drives>VLT AutomationDrive FC 300

Danfoss VLT AutomationDrive FC 300 Programming Guide

Danfoss VLT AutomationDrive FC 300
277 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #205 background imageLoading...
Page #205 background image
3.15.9 14-8* Options
14-80 Option Supplied by External 24VDC
Option: Function:
[0] No Select No [0] to use the drive's 24 V DC supply.
[1] * Yes Select Yes [1] if an external 24 V DC supply will be used to power the option. Inputs/Outputs will
be galvanically isolated from the drive when operated from an external supply.
NB!
This parameter is only changing function by performing a power cycle.
14-90 Fault Level
Option: Function:
[0] * Off Use this parameter to customize Fault levels. Use [0] "Off" with caution as it will ignore all Warnings
& Alarms for the chosen source.
[1] Warning
[2] Trip
[3] Trip Lock
Failure Alarm Off Warning Trip Trip Lock
10V low 1 X X *
24V low 47 X X*
1.8V supply low 48 X X*
Voltage limit 64 X X*
Earth fault during ramping 14 X* X
Earth fault 2 during cont. operation 45 X* X
Torque Limit 12 X X*
Table 3.4: Table for selection of choice of action when selected alarm appear:
3 Parameter descriptions FC 300 Programming Guide
204
MG.33.M8.02 - VLT
®
is a registered Danfoss trademark
3

Other manuals for Danfoss VLT AutomationDrive FC 300

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AutomationDrive FC 300 and is the answer not in the manual?

Danfoss VLT AutomationDrive FC 300 Specifications

General IconGeneral
BrandDanfoss
ModelVLT AutomationDrive FC 300
CategoryDC Drives
LanguageEnglish

Related product manuals