35-45 Term. X48/2 High Ref./Feedb. Value
Range: Function:
100.000* [-999999.999 - 999999.999 ] Enter the reference or feedback value (in RPM, Hz, bar, etc.) that corresponds to the voltage or
current set in par. 35-43.
35-46 Term. X48/2 Filter Time Constant
Range: Function:
0.001 s* [0.001 - 10.000 s] Enter the filter time constant. This is a first-order digital low pass filter time constant for suppressing
electrical noise in terminal X48/2. A high time constant value improves dampening but also increases
the time delay through the filter.
3 Parameter descriptions FC 300 Programming Guide
232
MG.33.M8.02 - VLT
®
is a registered Danfoss trademark
3