EasyManua.ls Logo

Danfoss VLT AutomationDrive FC 300 - Page 82

Danfoss VLT AutomationDrive FC 300
277 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
3.5.7 3-7* Ramp 4
Configure ramp parameters, see 3-4*.
3-70 Ramp 4 Type
Option: Function:
Select the ramp type, depending on requirements for acceleration and deceleration. A linear ramp
will give constant acceleration during ramping. An S-ramp will give non-linear acceleration, com-
pensating for jerk in the application
[0] * Linear
[1] S-ramp Const Jerk Accelerates with lowest possible jerk.
[2] S-ramp Const Time S-ramp based on the values set in par. 3-71
Ramp 4 Ramp up Time
and par. 3-72
Ramp 4 Ramp
Down Time
.
NB!
If S-ramp [1] is selected and the reference during ramping is changed the ramp time may be prolonged in order to realize a jerk free
movement which may result in a longer start or stop time.
Additional adjustment of the S-ramp ratios or switching initiators may be necessary.
3-71 Ramp 4 Ramp up Time
Range: Function:
Application
dependent*
[Application dependant] Enter the ramp-up time, i.e. the acceleration time from 0 RPM to the rated motor speed n
s
. Choose
a ramp-up time such that the output current does not exceed the current limit in par. 4-18
Current
Limit
during ramping. The value 0.00 corresponds to 0.01 sec. in speed mode. See ramp-down time
in par. 3-72
Ramp 4 Ramp Down Time
.
Par
. 3 71 =
t
acc
s
x
n
s
RPM
ref
RPM
3-72 Ramp 4 Ramp Down Time
Range: Function:
Application
dependent*
[Application dependant] Enter the ramp-down time, i.e. the deceleration time from the rated motor speed n
s
to 0 RPM.
Choose a ramp-down time such that no over-voltage arises in the inverter due to regenerative
operation of the motor, and such that the generated current does not exceed the current limit set
in par. 4-18
Current Limit
. The value 0.00 corresponds to 0.01 s in speed mode. See ramp-up time
in par. 3-71
Ramp 4 Ramp up Time
.
Par
. 3 72 =
t
dec
s
x
n
s
RPM
ref
RPM
3-75 Ramp 4 S-ramp Ratio at Accel. Start
Range: Function:
50 %* [Application dependant] Enter the proportion of the total ramp-up time (par. 3-71
Ramp 4 Ramp up Time
) in which the
acceleration torque increases. The larger the percentage value, the greater the jerk compensation
achieved, and thus the lower the torque jerks in the application.
3-76 Ramp 4 S-ramp Ratio at Accel. End
Range: Function:
50 %* [Application dependant] Enter the proportion of the total ramp-up time (par. 3-71
Ramp 4 Ramp up Time
) in which the
acceleration torque decreases. The larger the percentage value, the greater the jerk compensation
achieved, and thus the lower the torque jerks in the application.
FC 300 Programming Guide 3 Parameter descriptions
MG.33.M8.02 - VLT
®
is a registered Danfoss trademark
81
3

Other manuals for Danfoss VLT AutomationDrive FC 300

Related product manuals