4-58 Missing Motor Phase Function
Displays an alarm in the event of a missing motor phase (alarm 30, 31 or 32). Select disabled for no missing motor phase alarm. It is strongly
recommended to make an active setting to avoid motor damage.
Option: Function:
[0] Disabled No alarm is displayed if a missing motor phase occurs.
[1] Trip 100 ms Trips after 100ms. Select 100 ms for fast detection of missing motor phase.
[2] Trip 1000 ms Trips after 1000 ms. Select 1000 ms for slow detection of missing motor phase.
[3] Trip 100 ms lim 3 phase detec.
NB!
This parameter cannot be adjusted while the motor is running.
3.6.5 4-6* Speed Bypass
Define the Speed Bypass areas for the ramps.
Some systems call for avoiding certain output frequencies or speeds, due to resonance problems in the system. A maximum of four frequency or speed
ranges can be avoided.
4-60 Bypass Speed From [RPM]
Array [4]
Range: Function:
Application
dependent*
[Application dependant] Some systems call for avoiding certain output speeds due to resonance problems in the system.
Enter the lower limits of the speeds to be avoided.
4-61 Bypass Speed From [Hz]
Array [4]
Range: Function:
Application
dependent*
[Application dependant] Some systems call for avoiding certain output speeds due to resonance problems in the system.
Enter the lower limits of the speeds to be avoided.
4-62 Bypass Speed To [RPM]
Array [4]
Range: Function:
Application
dependent*
[Application dependant] Some systems call for avoiding certain output speeds due to resonance problems in the system.
Enter the upper limits of the speeds to be avoided.
4-63 Bypass Speed To [Hz]
Array [4]
Range: Function:
Application
dependent*
[Application dependant] Some systems call for avoiding certain output speeds due to resonance problems in the system.
Enter the upper limits of the speeds to be avoided.
FC 300 Programming Guide 3 Parameter descriptions
MG.33.M8.02 - VLT
®
is a registered Danfoss trademark
91
3

Other manuals for Danfoss VLT AutomationDrive FC 300

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AutomationDrive FC 300 and is the answer not in the manual?

Danfoss VLT AutomationDrive FC 300 Specifications

General IconGeneral
BrandDanfoss
ModelVLT AutomationDrive FC 300
CategoryDC Drives
LanguageEnglish

Related product manuals