EasyManuals Logo

Danfoss VLT AutomationDrive FC 301 Programming Guide

Danfoss VLT AutomationDrive FC 301
722 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #212 background imageLoading...
Page #212 background image
Option
Name
Description
[47]
Bus ctrl, 0 if timeout
Controls output via bus. The state of the output is set in parameter 5-90 Digital & Relay Bus
Control. If a bus timeout occurs, the output state is set low (off).
[50]
On reference
[51]
MCO controlled
[59]
Remote, enable, no TW
[60]
Comparator 0
See parameter group 13-1* Comparators. If comparator 0 in SLC is true, the output goes high.
Otherwise, it is low.
[61]
Comparator 1
See parameter group 13-1* Comparators. If comparator 1 in SLC is true, the output goes high.
Otherwise, it is low.
[62]
Comparator 2
See parameter group 13-1* Comparators. If comparator 2 in SLC is true, the output goes high.
Otherwise, it is low.
[63]
Comparator 3
See parameter group 13-1* Comparators. If comparator 3 in SLC is true, the output goes high.
Otherwise, it is low.
[64]
Comparator 4
See parameter group 13-1* Comparators. If comparator 4 in SLC is true, the output goes high.
Otherwise, it is low.
[65]
Comparator 5
See parameter group 13-1* Comparators. If comparator 5 in SLC is true, the output goes high.
Otherwise, it is low.
[66]
Comparator 6
See parameter group 13-1* Comparators. If comparator 6 in SLC is true, the output goes high.
Otherwise, it is low.
[67]
Comparator 7
See parameter group 13-1* Comparators. If comparator 7 in SLC is true, the output goes high.
Otherwise, it is low.
[68]
Comparator 8
See parameter group 13-1* Comparators. If comparator 8 in SLC is true, the output goes high.
Otherwise, it is low.
[69]
Comparator 9
See parameter group 13-1* Comparators. If comparator 9 in SLC is true, the output goes high.
Otherwise, it is low.
[70]
Logic rule 0
See parameter group 13-4* Logic Rules. If logic rule 0 in SLC is true, the output goes high. Oth-
erwise, it is low.
[71]
Logic rule 1
See parameter group 13-4* Logic Rules. If logic rule 1 in SLC is true, the output goes high. Oth-
erwise, it is low.
[72]
Logic rule 2
See parameter group 13-4* Logic Rules. If logic rule 2 in SLC is true, the output goes high. Oth-
erwise, it is low.
[73]
Logic rule 3
See parameter group 13-4* Logic Rules. If logic rule 3 in SLC is true, the output goes high. Oth-
erwise, it is low.
[74]
Logic rule 4
See parameter group 13-4* Logic Rules. If logic rule 4 in SLC is true, the output goes high. Oth-
erwise, it is low.
[75]
Logic rule 5
See parameter group 13-4* Logic Rules. If logic rule 5 in SLC is true, the output goes high. Oth-
erwise, it is low.
[76]
Logic rule 6
See parameter group 13-4* Logic Rules. If logic rule 6 in SLC is true, the output goes high. Oth-
erwise, it is low.
[77]
Logic rule 7
See parameter group 13-4* Logic Rules. If logic rule 7 in SLC is true, the output goes high. Oth-
erwise, it is low.
AU275636650261en-000101 / 130R0334212 | Danfoss A/S © 2022.12
Parameter Descriptions
VLT AutomationDrive FC 301/302
Programming Guide

Table of Contents

Other manuals for Danfoss VLT AutomationDrive FC 301

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AutomationDrive FC 301 and is the answer not in the manual?

Danfoss VLT AutomationDrive FC 301 Specifications

General IconGeneral
BrandDanfoss
ModelVLT AutomationDrive FC 301
CategoryDC Drives
LanguageEnglish

Related product manuals