EasyManua.ls Logo

Danfoss VLT AutomationDrive FC 302 - Page 169

Danfoss VLT AutomationDrive FC 302
212 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
10.14.1 EMC Test Results
The following test results have been obtained using a drive (with options if relevant), a shielded control cable, a control box
with potentiometer, a motor, and motor shielded cable.
RFI lter type Conducted emission Radiated emission
Standards and
requirements
EN 55011 Class B
Housing,
trades, and
light
industries
Class A
group 1
Industrial
environment
Class A
group 2
Industrial
environment
Class B
Housing, trades,
and light
industries
Class A
group 1
Industrial
environment
Class A
group 2
Industrial
environment
EN/IEC 61800-3 Category C1
First
environment
Home and
oce
Category C2
First
environment
Home and
oce
Category C3
Second
environment
Industrial
Category C1
First
environment
Home and oce
Category C2
First environment
Home and oce
Category C3
First
environment
Home and
oce
H2
FC 302 90–500 kW
380–500 V
No No 150 m
(492 ft)
No No Yes
55–710 kW
525–690 V
No No 150 m
(492 ft)
No No Yes
H4
FC 302 90–500 kW
380–500 V
No 150 m
(492 ft)
150 m
(492 ft)
No Yes Yes
55–710 kW
525–690 V
Table 10.37 EMC Test Results (Emission and Immunity)
10.14.2 Emission Requirements
According to the EMC product standard for adjustable speed drives EN/IEC 61800-3:2004, the EMC requirements depend on
the environment in which the drive is installed. These environments along with the mains voltage supply requirements are
dened in Table 10.38.
The drives comply with EMC requirements described in IEC/EN 61800-3 (2004)+AM1 (2011), category C3, for equipment
having greater than 100 A per-phase current draw, installed in the second environment. Compliance testing is performed
with a 150 m (492 ft) shielded motor cable.
Category
(EN 61800-3)
Denition Conducted emission
(EN 55011)
C1 First environment (home and oce) with a supply voltage less than 1000 V. Class B
C2 First environment (home and oce) with a supply voltage less than 1000 V, which
is not plug-in or movable and where a professional is intended to be used to
install or commission the system.
Class A Group 1
C3 Second environment (industrial) with a supply voltage lower than 1000 V. Class A Group 2
C4 Second environment with the following:
Supply voltage equal to or above 1000 V.
Rated current equal to or above 400 A.
Intended for use in complex systems.
No limit line.
An EMC plan must be made.
Table 10.38 Emission Requirements
When the generic emission standards are used, the drives are required to comply with Table 10.39.
Electrical Installation Con... Design Guide
MG38C202 Danfoss A/S © 01/2018 All rights reserved. 167
10 10

Table of Contents

Other manuals for Danfoss VLT AutomationDrive FC 302