Environment Generic standard Conducted emission requirement
according to EN 55011 limits
First environment
(home and oce)
EN/IEC 61000-6-3 Emission standard for residential, commercial,
and light industrial environments.
Class B
Second environment
(industrial environment)
EN/IEC 61000-6-4 Emission standard for industrial environments. Class A Group 1
Table 10.39 Generic Emission Standard Limits
10.14.3 Immunity Requirements
The immunity requirements for drives depend on the installation environment. The requirements for the industrial
environment are higher than the requirements for the home and oce environment. All Danfoss drives comply with the
requirements for both the industrial and the home/oce environment.
To document immunity against burst transient, the following immunity tests have been performed on a drive (with options
if relevant), a shielded control cable, and a control box with potentiometer, motor cable, and motor. The tests were
performed in accordance with the following basic standards. For more details, see Table 10.40.
EN 61000-4-2 (IEC 61000-4-2): Electrostatic discharges (ESD): Simulation of electrostatic discharges from human
beings.
EN 61000-4-3 (IEC 61000-4-3): Incoming electromagnetic
eld radiation, amplitude modulated simulation of the
eects of radar, radio communication equipment, and mobile communications equipment.
EN 61000-4-4 (IEC 61000-4-4): Burst transients: Simulation of interference brought about by switching a contactor,
relay, or similar devices.
EN 61000-4-5 (IEC 61000-4-5): Surge transients: Simulation of transients brought about by lightning strikes near
installations.
EN 61000-4-6 (IEC 61000-4-6): RF common mode: Simulation of the eect from radio-transmission equipment
joined by connection cables.
Basic standard Burst
IEC 61000-4-4
Surge
IEC 61000-4-5
ESD
IEC
61000-4-2
Radiated
electro-magnetic eld
IEC 61000-4-3
RF common
mode voltage
IEC 61000-4-6
Acceptance criterion B B B A A
Line 4 kV CM
2 kV/2 Ω DM
4 kV/12 Ω CM
10 V
RMS
Motor 4 kV CM
4 kV/2 Ω
1)
10 V
RMS
Brake 4 kV CM
4 kV/2 Ω
1)
10 V
RMS
Load sharing 4 kV CM
4 kV/2 Ω
1)
10 V
RMS
Control wires 2 kV CM
2 kV/2 Ω
1)
10 V
RMS
Standard bus 2 kV CM
2 kV/2 Ω
1)
10 V
RMS
Relay wires 2 kV CM
2 kV/2 Ω
1)
10 V
RMS
Application/eldbus options 2 kV CM
2 kV/2 Ω
1)
10 V
RMS
LCP cable 2 kV CM
2 kV/2 Ω
1)
10 V
RMS
External 24 V DC 2 V CM
0.5 kV/2 Ω DM
1 kV/12 Ω CM
10 V
RMS
Enclosure 8 kV AD
6 kV CD
10 V/m
Table 10.40 EMC Immunity Form, Voltage Range: 380–480/500 V, 525–600 V, 525–690 V
1) Injection on cable shield.
AD: air discharge; CD: contact discharge; CM: common mode; DM: dierential mode.
Electrical Installation Con... VLT® AutomationDrive FC 302
168 Danfoss A/S © 01/2018 All rights reserved. MG38C202