Bit Hex Dec
Alarm word
(parameter 1
6-90 Alarm
Word)
Alarm word
2
(parameter
16-91 Alarm
Word 2)
Alarm word
3
(parameter 1
6-97 Alarm
Word 3)
Warning word
(parameter 16-
92 Warning
Word)
Warning word
2
(parameter 16
-93 Warning
Word 2)
Extended
status word
(parameter 16-
94 Ext. Status
Word)
Extended
status word 2
(parameter 16-95 Ext
. Status Word 2)
23
008000
00
8388608
24 V supply
low
Position ctrl.
fault
Reserved
24 V supply
low
Reserved Reserved Running
24
010000
00
16777216 Mains failure
Tension
Limit
Reserved Mains failure Reserved Reserved Bypass
25
020000
00
33554432 Reserved Current limit Reserved Current limit Reserved Reserved Reserved
26
040000
00
67108864
Brake
resistor
Reserved Reserved Reserved Reserved Reserved External interlock
27
080000
00
13421772
8
Brake IGBT Reserved Reserved Reserved Reserved Reserved Reserved
28
100000
00
26843545
6
Option
change
Feedback
fault
Reserved Encoder loss Reserved Reserved FlyStart active
29
200000
00
53687091
2
Frequency
converter
initialized
Encoder loss Reserved Reserved
Back EMF too
high
Reserved
Heat sink clean
warning
30
400000
00
10737418
24
Reserved Reserved Reserved Reserved Reserved Reserved Reserved
31
800000
00
21474836
48
Mech. brake
low
Reserved Reserved Reserved Reserved Database busy Reserved
Table 7.2 Description of Alarm Word, Warning Word, and Extended Status Word
Diagnostics and Troubleshoo...
VLT
®
AutomationDrive FC 360
50 Danfoss A/S © 03/2017 All rights reserved. MG06A702