Bit Hex Dec
Alarm word
(parameter 1
6-90 Alarm
Word)
Alarm word
2
(parameter
16-91 Alarm
Word 2)
Alarm word
3
(parameter 1
6-97 Alarm
Word 3)
Warning word
(parameter 16-
92 Warning
Word)
Warning word
2
(parameter 16
-93 Warning
Word 2)
Extended
status word
(parameter 16-
94 Ext. Status
Word)
Extended
status word 2
(parameter 16-95 Ext
. Status Word 2)
0
000000
01
1 Brake check Reserved Reserved Reserved Reserved Ramping O
1
000000
02
2
Pwr. card
temp
Gate drive
voltage fault
Reserved
Pwr. card
temp
Reserved AMA tuning Hand/Auto
2
000000
04
4 Earth fault Reserved Reserved Reserved Reserved Start CW/CCW
PROFIBUS OFF1
active
3
000000
08
8
Ctrl. card
temp
Reserved Reserved Ctrl. card temp Reserved Slowdown
PROFIBUS OFF2
active
4
000000
10
16
Ctrl. word
TO
Illegal FC
cong
Reserved Ctrl. word TO Reserved Catch up
PROFIBUS OFF3
active
5
000000
20
32 Overcurrent Reserved Reserved Overcurrent Reserved Feedback high Reserved
6
000000
40
64 Torque limit Reserved Reserved Torque limit Reserved Feedback low Reserved
7
000000
80
128
Motor Th.
over
Reserved Reserved Motor Th. over Reserved
Output current
high
Control ready
8
000001
00
256
Motor ETR
over
Broken belt Reserved
Motor ETR
over
Broken belt
Output current
low
Frequency converter
ready
9
000002
00
512
Inverter
overld.
Reserved Reserved Inverter overld. Reserved
Output freq.
high
Quick stop
10
000004
00
1024
DC
undervolt.
Start failed Reserved DC undervolt. Reserved
Output freq.
low
DC brake
11
000008
00
2048 DC overvolt. Reserved Reserved DC overvolt. Reserved Brake check OK Stop
12
000010
00
4096 Short circuit
External
interlock
Reserved Reserved Reserved Braking max Latched
13
000020
00
8192 Reserved Reserved Reserved Reserved Reserved Braking Reserved
14
000040
00
16384
Mains ph.
loss
Reserved Reserved Mains ph. loss Reserved Reserved Freeze output
15
000080
00
32768 AMA not OK Reserved Reserved No motor Auto DC brake OVC active Reserved
16
000100
00
65536
Live zero
error
Reserved Reserved Live zero error Reserved AC brake Jog
17
000200
00
131072 Internal fault Reserved Reserved Reserved Reserved Reserved Reserved
18
000400
00
262144
Brake
overload
Reserved Reserved
Brake resistor
power limit
Reserved Reserved Start
19
000800
00
524288 U phase loss Reserved Reserved Reserved Reserved Reference high Reserved
20
001000
00
1048576 V phase loss
Option
detection
Reserved Reserved Overload T27 Reference low Start delay
21
002000
00
2097152 W phase loss Option fault Reserved Reserved Reserved Reserved Sleep
22
004000
00
4194304
Fieldbus
fault
Locked rotor Reserved Fieldbus fault Reserved Reserved Sleep boost
Diagnostics and Troubleshoo... Quick Guide
MG06A702 Danfoss A/S © 03/2017 All rights reserved. 49
7 7

Other manuals for Danfoss VLT AutomationDrive FC 360

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AutomationDrive FC 360 and is the answer not in the manual?

Danfoss VLT AutomationDrive FC 360 Specifications

General IconGeneral
BrandDanfoss
ModelVLT AutomationDrive FC 360
CategoryDC Drives
LanguageEnglish

Related product manuals