11.1.2 Derating for Temperature
The frequency converter automatically derates the
switching frequency, switching type, or output current
under certain load or ambient conditions as described
below. The derating curves in Illustration 11.1 and
Illustration 11.2 apply to both SFAVM and 60 AVM
switching modes.
130BX491.10
Iout [%]
fsw
[kHz]
o
70
80
90
0.5
60
100
110
2.0
50 C
55 C
0.0
o
1.0 1.5 2.5 4.03.0 3.5
o
45 C
Illustration 11.1 Derating Frame Sizes D, E, and F 380-500 V
(T5) High Overload 150%
130BX492.10
o
70
80
90
0.5
Iout [%]
60
100
110
2.0
fsw
[kHz]
50 C
55 C
0.0
o
1.0 1.5 2.5 4.03.0 3.5
o
45 C
o
40 C
50
Illustration 11.2 Derating Frame Sizes D, E, and F 380-500 V
(T5) Normal Overload 110%
Specifications Operating Instructions
142 Danfoss A/S © Rev. 2014-07-29 All rights reserved. MG37A202
1111

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT FC 302 and is the answer not in the manual?

Danfoss VLT FC 302 Specifications

General IconGeneral
Brake FunctionBuilt-in brake chopper in all units up to 22 kW
Output Voltage Range0-100% of input voltage
Power Range0.37 kW
Control ModesVVCplus, Flux, U/f
Protection FeaturesOvervoltage, undervoltage, overcurrent, short circuit, overtemperature, overload
Communication OptionsModbus RTU, BACnet, Ethernet/IP, Profinet, Profibus, CANopen, DeviceNet
Ambient Temperature Range-10°C to +50°C (derating above +40°C)
Enclosure RatingIP20, IP21, IP55
Cooling MethodAir-cooled
Input Voltage200-240V, 380-480V, 525-600V

Related product manuals