power to the frequency converter, basic programming,
set-up, and functional testing.
4.5 System Start Up
Complete user wiring and application programming before
performing the procedure in this section. See
chapter 7 Application Examples for application set-up
information. The following procedure is recommended
after application set-up by the user is completed.
CAUTION
MOTOR START!
Ensure that the motor, system, and any attached
equipment are ready for start. It is the responsibility of
the user to ensure safe operation under any condition.
Failure to ensure that the motor, system, and any
attached equipment are ready for start could result in
personal injury or equipment damage.
1. Press [Auto On].
2. Ensure that external control functions are
properly wired to the frequency converter and all
programming is completed.
3. Apply an external run command.
4. Adjust the speed reference throughout the speed
range.
5. Remove the external run command.
6. Note any problem.
If warnings or alarms occur, see chapter 9 Warnings and
Alarms.