EasyManuals Logo
Home>Danfoss>Controller>VLT FC 302

Danfoss VLT FC 302 User Manual

Danfoss VLT FC 302
164 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #28 background imageLoading...
Page #28 background image
3.4.2 Extra Protection (RCD)
ELCB relays, multiple protective grounding, or standard
grounding provide extra protection, if local safety
regulations are followed.
In the case of a ground fault, a DC component develops in
the fault current.
If using ELCB relays, observe local regulations. Relays must
be suitable for protection of 3-phase equipment with a
bridge rectifier and for a brief discharge on power-up.
3.4.3
RFI Switch
Mains supply isolated from ground
If the frequency converter is supplied from an isolated
mains source or TT/TN-S mains with grounded leg, turn off
the RFI switch via 14-50 RFI Filter on both frequency
converter and the filter. For further reference, see IEC
364-3. When optimum EMC performance is needed,
parallel motors are connected, or the motor cable length is
above 25 m, set 14-50 RFI Filter to [ON].
In OFF, the internal RFI capacitors (filter capacitors)
between the chassis and the intermediate circuit are cut
off to avoid damage to the intermediate circuit and reduce
ground capacity currents (IEC 61800-3).
Refer to the application note VLT on IT mains. It is
important to use isolation monitors that work together
with power electronics (IEC 61557-8).
3.4.4
Shielded Cables
It is important to connect shielded cables properly to
ensure high EMC immunity and low emissions.
Connection can be made using either cable glands or
clamps:
EMC cable glands: Generally available cable
glands can be used to ensure an optimum EMC
connection.
EMC cable clamp: Clamps allowing easy
connection are supplied with the unit.
3.4.5
Motor Cable
Connect the motor to terminals U/T1/96, V/T2/97, W/T3/98,
on the far right of the unit. Ground to terminal 99. All
types of 3-phase asynchronous standard motors can be
used with a frequency converter. The factory setting is for
clockwise rotation with the frequency converter output
connected as follows:
Terminal No. Function
96, 97, 98
99
Mains U/T1, V/T2, W/T3
Ground
Table 3.4 Terminal Functions
Terminal U/T1/96 connected to U-phase
Terminal V/T2/97 connected to V-phase
Terminal W/T3/98 connected to W-phase
The direction of rotation can be changed by switching 2
phases in the motor cable or by changing the setting of
4-10 Motor Speed Direction.
Motor rotation check can be performed via 1-28 Motor
Rotation Check and following the steps shown in the
display.
175HA036.11
U
1
V
1
W
1
96 97 98
FC
Motor
U
2
V
2
W
2
U
1
V
1
W
1
96 97 98
FC
Motor
U
2
V
2
W
2
Illustration 3.18 Motor Rotation Check
F-frame requirements
Use motor phase cables in quantities of 2, resulting in 2, 4,
6, or 8 to obtain an equal number of wires on both
inverter module terminals. The cables are required to be
equal length within 10% between the inverter module
terminals and the first common point of a phase. The
recommended common point is the motor terminals.
Installation
Operating Instructions
26 Danfoss A/S © Rev. 2014-07-29 All rights reserved. MG37A202
33

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT FC 302 and is the answer not in the manual?

Danfoss VLT FC 302 Specifications

General IconGeneral
BrandDanfoss
ModelVLT FC 302
CategoryController
LanguageEnglish

Related product manuals