Torque characteristics
Starting torque (constant torque) maximum 160% for 1 m
1)
Starting torque maximum 180% up to 0.5 s
1)
Overload torque (constant torque) maximum 160% for 1 m
1)
1) Percentage relates to nominal torque of the unit.
Cable lengths and cross-sections
Max. motor cable length, screened/armoured 150 m
Max. motor cable length, unscreened/unarmoured 300 m
Max. cross-section to motor, mains, load sharing, and brake
1)
Maximum cross-section to control terminals, rigid wire 1.5 mm
2
/16 AWG (2 x 0.75 mm
2
)
Maximum cross-section to control terminals, flexible cable 1 mm
2
/18 AWG
Maximum cross-section to control terminals, cable with enclosed core 0.5 mm
2
/20 AWG
Minimum cross-section to control terminals 0.25 mm
2
1) See chapter 11.1.1 Mains Supply 3x380-480 V AC for more information
Digital inputs
Programmable digital inputs 4 (6)
Terminal number 18, 19, 27
1)
, 29
1)
, 32, 33,
Logic PNP or NPN
Voltage level 0-24 V DC
Voltage level, logic'0' PNP < 5 V DC
Voltage level, logic'1' PNP > 10 V DC
Voltage level, logic '0' NPN > 19 V DC
Voltage level, logic '1' NPN < 14 V DC
Maximum voltage on input 28 V DC
Input resistance, R
i
approx. 4 k
All digital inputs are galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.
1) Terminals 27 and 29 can also be programmed as output.
Analog inputs
Number of analog inputs 2
Terminal number 53, 54
Modes Voltage or current
Mode select Switch S201 and switch S202
Voltage mode Switch S201/switch S202 = OFF (U)
Voltage level 0 to + 10 V (scaleable)
Input resistance, R
i
approx. 10 k
Max. voltage ± 20 V
Current mode Switch S201/switch S202 = ON (I)
Current level 0/4 to 20 mA (scaleable)
Input resistance, R
i
approx. 200
Max. current 30 mA
Resolution for analog inputs 10 bit (+ sign)
Accuracy of analog inputs Max. error 0.5% of full scale
Bandwidth 200 Hz
The analog inputs are galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.
Specifications
Operating Instructions
146 Danfoss A/S © Rev. 2014-07-29 All rights reserved. MG37A202
1111