Connection to PC is carried out via a standard host/device USB cable. The USB connection is galvanically isolated from the
supply voltage (PELV) and other high-voltage terminals. The USB connection is not galvanically isolated from protective
earth. Use only isolated laptop/PC as connection to the USB connector on the unit or an isolated USB cable/converter.
Protection and features
Temperature monitoring of the heat sink ensures that the active filter trips if the temperature reaches a predefined
level. An overload temperature cannot be reset until the temperature of the heat sink is below the acceptable
values.
If a mains phase is missing, the active filter trips.
The active filter has a short circuit protection current rate of 100 kA if properly fused
Monitoring of the intermediate circuit voltage ensures that the filter trips if the intermediate circuit voltage is too
low or too high.
The active filter monitors the mains current as well as internal currents to reassure that current levels do not reach
critical levels. If current exceeds a critical level, the filter trips.
Specifications Operating Instructions
152 Danfoss A/S © Rev. 2014-07-29 All rights reserved. MG37A202
1111

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT FC 302 and is the answer not in the manual?

Danfoss VLT FC 302 Specifications

General IconGeneral
Brake FunctionBuilt-in brake chopper in all units up to 22 kW
Output Voltage Range0-100% of input voltage
Power Range0.37 kW
Control ModesVVCplus, Flux, U/f
Protection FeaturesOvervoltage, undervoltage, overcurrent, short circuit, overtemperature, overload
Communication OptionsModbus RTU, BACnet, Ethernet/IP, Profinet, Profibus, CANopen, DeviceNet
Ambient Temperature Range-10°C to +50°C (derating above +40°C)
Enclosure RatingIP20, IP21, IP55
Cooling MethodAir-cooled
Input Voltage200-240V, 380-480V, 525-600V