EasyManuals Logo
Home>Danfoss>DC Drives>VLT FC 360

Danfoss VLT FC 360 User Manual

Danfoss VLT FC 360
82 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #43 background imageLoading...
Page #43 background image
3 RS-485 Installation and Set-up
3.1 Introduction
3.1.1 Overview
RS-485 is a two-wire bus interface compatible with multi-
drop network topology, that is, nodes can be connected as
a bus, or via drop cables from a common trunk line. A
total of 32 nodes can be connected to one network
segment.
Repeaters divide network segments.
NOTE
Each repeater functions as a node within the segment in
which it is installed. Each node connected within a given
network must have a unique node address, across all
segments.
Terminate each segment at both ends, using either the
termination switch (S801) of the frequency converters or a
biased termination resistor network. Always use screened
twisted pair (STP) cable for bus cabling, and always follow
good common installation practice.
Low-impedance earth connection of the screen at every
node is important, including at high frequencies. Thus,
connect a large surface of the screen to earth, for example
with a cable clamp or a conductive cable gland. It may be
necessary to apply potential-equalizing cables to maintain
the same earth potential throughout the network - partic-
ularly in installations with long cables.
To prevent impedance mismatch, always use the same
type of cable throughout the entire network. When
connecting a motor to the frequency converter, always use
screened motor cable.
Cable
Screened twisted pair (STP)
Impedance
[Ω]
120
Cable length
[m]
Max. 1200 (including drop lines)
Max. 500 station-to-station
Table 3.1 Cable
3.1.2
Network Connection
Connect the frequency converter to the RS-485 network
as follows (see also Illustration 3.1):
1. Connect signal wires to terminal 68 (P+) and
terminal 69 (N-) on the main control board of the
frequency converter.
2. Connect the cable screen to the cable clamps.
NOTE
Screened, twisted-pair cables are recommended in order to
reduce noise between conductors.
61 68 69
N
P
COMM. GND
130BB795.10
Illustration 3.1 Network Connection
3.1.3 Frequency Converter Hardware Set-
up
Use the terminator switch on the main control board of
the frequency converter to terminate the RS-485 bus.
The factory setting for the switch is OFF.
3.1.4
Frequency Converter Parameter
Settings for Modbus Communication
Define the RS-485 Communicaiton Set-up
Parameter Function
8-30 Protocol Select the application protocol to run on
the RS-485 interface
8-31 Address Set the node address.
NOTE
The address range depends on the
protocol selected in 8-30 Protocol
8-32 Baud Rate Set the baud rate.
NOTE
The default baud rate depends on the
protocol selected in 8-30 Protocol
8-33 Parity / Stop
Bits
Set the parity and number of stop bits.
NOTE
The default selection depends on the
protocol selected in 8-30 Protocol
8-35 Minimum
Response Delay
Specify a minimum delay time between
receiving a request and transmitting a
response. This function is for overcoming
modem turnaround delays.
RS-485 Installation and Set...
VLT
®
AutomationDrive FC 360 Design Guide
MG06B202 - VLT
®
is a registered Danfoss trademark 41
3
3

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT FC 360 and is the answer not in the manual?

Danfoss VLT FC 360 Specifications

General IconGeneral
BrandDanfoss
ModelVLT FC 360
CategoryDC Drives
LanguageEnglish

Related product manuals