6.2 General Specifications
Mains supply (L1, L2, L3)
Supply Terminals L1, L2, L3
Supply voltage 380-480 V:-15% (-25%)
1)
to +10%
1) The frequency converter can run at -25% input voltage with reduced performance. The maximum output power of the
frequency converter is 75% in case of -25% input voltage and 85% in case of -15% input voltage.
Mains voltage low/mains drop-out:
During low mains voltage or a mains drop-out, the frequency converter continues until the intermediate circuit voltage drops
below the minimum stop level, which corresponds typically to 15% below the frequency converter's lowest rated supply voltage.
Full torque cannot be expected at mains voltage lower than 10% below the frequency converter's lowest rated supply voltage.
Supply frequency 50/60 Hz ±5%
Max. imbalance temporary between mains phases 3.0 % of rated supply voltage
True Power Factor (λ) ≥ 0.9 nominal at rated load
Displacement Power Factor (cos ϕ) near unity (> 0.98)
Switching on input supply L1, L2, L3 (power-ups) ≤ 7.5 kW maximum 2 times/min.
Switching on input supply L1, L2, L3 (power-ups) 11-75 kW maximum 1 time/min.
The unit is suitable for use on a circuit capable of delivering not more than 100,000 RMS symmetrical Amperes, 480 V maximum.
Motor output (U, V, W)
Output voltage 0-100% of supply voltage
Output frequency (0.37-75 kW) 0-500 Hz
Output frequency in VVC
plus
Mode 0-200 Hz
Switching on output Unlimited
Ramp times 0.01-3600 s
Torque characteristics
Starting torque (constant torque) maximum 160% for 60 s
1)
Overload torque (constant torque) maximum 160% for 60 s
1)
Starting torque (variable torque) maximum 110% for 60 s
1)
Overload torque (variable torque) maximum 110% for 60 s
Starting current maximum 200% for 1 s
Torque rise time in VVC
plus
(independent of fsw) 10 ms
1)
Percentage relates to the nominal torque.
2)
The torque response time depends on application and load but as a general rule, the torque step from 0 to reference is 4-5 x
torque rise time.
Control cable lengths and cross sections
1)
Max. motor cable length, screened 50 m
Max. motor cable length, unscreened 100 m
Maximum cross section to control terminals, flexible/rigid wire 2.5 mm
2
/14 AWG
Minimum cross section to control terminals 0.55 mm
2
/ 30 AWG
1)
For power cables, see Table 6.1 to Table 6.3.
Digital inputs
Programmable digital inputs 7
Terminal number 18, 19, 27
1)
, 29
1)
, 32, 33, 31
Logic PNP or NPN
Voltage level 0-24 V DC
Voltage level, logic'0' PNP < 5 V DC
Voltage level, logic'1' PNP > 10 V DC
Voltage level, logic '0' NPN
2)
> 19 V DC
Voltage level, logic '1' NPN
2)
< 14 V DC
Maximum voltage on input 28 V DC
Pulse frequency range 4 Hz-32 kHz
(Duty cycle) Min. pulse width 4.5 ms
Specifications
VLT
®
AutomationDrive FC 360 Design Guide
MG06B202 - VLT
®
is a registered Danfoss trademark 69
6
6