What does L1-T1/L2-T2/L3-T3 shorted mean on a Danfoss VLT MCD 600?
A
Anthony CooleyAug 31, 2025
If the Danfoss Controller detects L1-T1, L2-T2, or L3-T3 Shorted, it means that during pre-start checks, the soft starter has detected a short-circuited SCR or a short circuit within the bypass contactor. Consider using PowerThrough to allow operation until the soft starter can be repaired. Also, see parameter 6-19 Shorted SCR Action.
T
Tammy VasquezSep 8, 2025
What does pressure sensor error mean on Danfoss VLT MCD 600 Controller?
B
Brenda SmithSep 8, 2025
If the Danfoss Controller displays a pressure sensor error, it means the smart card has detected a fault with the pressure sensor. Check the following parameters:
- Parameter 30-1 Pressure Sensor Type.
- Parameter 36-1 Pressure Sensor.
K
Kerry TuckerAug 29, 2025
What to do if Danfoss VLT MCD 600 Controller shows a power loss error?
A
Alyssa FletcherAug 29, 2025
If the Danfoss Controller displays a power loss error, it means the soft starter is not receiving mains supply on one or more phases. Check that the main contactor closes when a start command is given and remains closed until the end of a soft stop. Also, check the fuses. If testing the soft starter with a small motor, it must draw at least 10% of the programmed FLC setting on each phase.
R
rdunnSep 10, 2025
What to do when Danfoss VLT MCD 600 Controller shows high pressure?
J
jamie61Sep 12, 2025
If the Danfoss Controller indicates high pressure, the pressure sensor connected to the smart card has activated high-pressure protection. Check the following parameters:
- Parameter 30-1 Pressure Sensor Type.
- Parameter 30-3 Pressure at 4 mA.
- Parameter 30-4 Pressure at 20 mA.
- Parameter 32-1 High Pressure Trip Level.
- Parameter 32-2 High Pressure Start Delay.
- Parameter 32-3 High Pressure Response Delay.
- Parameter 36-4 High Pressure.
M
milesbradleySep 9, 2025
How to solve network communication problem with Danfoss VLT MCD 600 Controller?
S
Sheila CarterSep 10, 2025
If the Danfoss Controller displays a network communication error, the network master has sent a trip command to the soft starter, or there could be a network communication problem. Check the network for causes of communication inactivity. Check parameter 6-13 Network Communications.
D
David BarnesSep 13, 2025
What to do when Danfoss Controller shows low water?
R
Russell SmithSep 13, 2025
If the Danfoss Controller indicates low water, the depth sensor connected to the smart card has activated depth protection. Check the following parameters:
- Parameter 30-12 Depth Sensor Type.
- Parameter 30-14 Depth at 4 mA.
- Parameter 30-15 Depth at 20 mA.
- Parameter 34-1 Depth Trip Level.
- Parameter 34-2 Depth Reset Level.
- Parameter 34-3 Depth Start Relay.
- Parameter 36-9 Well Depth.
G
Gregory Anderson MDAug 27, 2025
What does overcurrent mean on a Danfoss VLT MCD 600?
Z
zrangelAug 27, 2025
If the Danfoss Controller shows an overcurrent, it means the current has exceeded the level set in parameter 5-5 for longer than the time set in parameter 5-6. This can be due to a momentary overload. Check the following parameters:
- Parameter 5-5 Overcurrent.
- Parameter 5-6 Overcurrent Delay.
- Parameter 6-5 Overcurrent.
M
Michael ConwayAug 26, 2025
What causes L1/L2/L3 phase loss in Danfoss Controller?
J
Julia MckayAug 26, 2025
If the Danfoss Controller detects a phase loss on L1, L2, or L3, it means that during pre-start checks, a phase loss was detected. In run state, it indicates that the current on the affected phase has dropped below 10% of the programmed motor FLC for more than 1 second, suggesting a loss of the incoming phase or a disconnection to the motor. Check the supply, input, and output connections for both the soft starter and the motor.
M
Mason GrayAug 25, 2025
How to resolve a motor overload error on a Danfoss VLT MCD 600 Controller?
C
caitlinspencerAug 26, 2025
If the motor has reached its maximum thermal capacity, the Danfoss Controller will show a motor overload. This can happen if the controller's protection settings don't match the motor's thermal capacity. Resolve the cause of the overload, allow the motor to cool down, and then check the following parameters:
- Parameter 1-2 Motor Full Load Current.
- Parameter 1-4 Locked Rotor Time.
- Parameter 1-5 Locked Rotor Current.
- Parameter 1-6 Motor Service Factor.
- Parameter 5-15 Excess Start Time.
- Parameter 6-10 Excess Start Time.
H
hbrennanAug 25, 2025
What to do if the Danfoss VLT MCD 600 Controller shows an instant overcurrent error?
K
Kimberly CooperAug 25, 2025
If the Danfoss Controller displays an instant overcurrent error, it means the current on all three phases has exceeded 7.2 times the value set for the motor's full load current. This could be due to a locked rotor or an electrical fault in the motor or cabling. Check for jammed loads and inspect the motor and cables for faults.