What does L1-T1/L2-T2/L3-T3 shorted mean on a Danfoss VLT MCD 600?
A
Anthony CooleyAug 31, 2025
If the Danfoss Controller detects L1-T1, L2-T2, or L3-T3 Shorted, it means that during pre-start checks, the soft starter has detected a short-circuited SCR or a short circuit within the bypass contactor. Consider using PowerThrough to allow operation until the soft starter can be repaired. Also, see parameter 6-19 Shorted SCR Action.
T
Tammy VasquezSep 8, 2025
What does pressure sensor error mean on Danfoss VLT MCD 600 Controller?
B
Brenda SmithSep 8, 2025
If the Danfoss Controller displays a pressure sensor error, it means the smart card has detected a fault with the pressure sensor. Check the following parameters:
- Parameter 30-1 Pressure Sensor Type.
- Parameter 36-1 Pressure Sensor.
K
Kerry TuckerAug 29, 2025
What to do if Danfoss VLT MCD 600 Controller shows a power loss error?
A
Alyssa FletcherAug 29, 2025
If the Danfoss Controller displays a power loss error, it means the soft starter is not receiving mains supply on one or more phases. Check that the main contactor closes when a start command is given and remains closed until the end of a soft stop. Also, check the fuses. If testing the soft starter with a small motor, it must draw at least 10% of the programmed FLC setting on each phase.
G
gutierrezjosephSep 23, 2025
What does rating capacity mean on Danfoss Controller?
J
jonathan26Sep 23, 2025
If the Danfoss Controller displays 'Rating Capacity', the soft starter is operating beyond its safe capacity. Allow the soft starter to cool.
M
milesbradleySep 9, 2025
How to solve network communication problem with Danfoss VLT MCD 600 Controller?
S
Sheila CarterSep 10, 2025
If the Danfoss Controller displays a network communication error, the network master has sent a trip command to the soft starter, or there could be a network communication problem. Check the network for causes of communication inactivity. Check parameter 6-13 Network Communications.
D
David BarnesSep 13, 2025
What to do when Danfoss Controller shows low water?
R
Russell SmithSep 13, 2025
If the Danfoss Controller indicates low water, the depth sensor connected to the smart card has activated depth protection. Check the following parameters:
- Parameter 30-12 Depth Sensor Type.
- Parameter 30-14 Depth at 4 mA.
- Parameter 30-15 Depth at 20 mA.
- Parameter 34-1 Depth Trip Level.
- Parameter 34-2 Depth Reset Level.
- Parameter 34-3 Depth Start Relay.
- Parameter 36-9 Well Depth.
V
Veronica MeyerSep 18, 2025
What does FLC too high mean on Danfoss VLT MCD 600 Controller?
C
Cynthia KimSep 18, 2025
If the Danfoss Controller displays 'FLC Too High', and the soft starter is connected to the motor using inside delta configuration, the soft starter may not be correctly detecting the connection. Set parameter 20-6 Motor Connection to the connection used for the motor (in-line or inside delta). If the failure remains, contact the local supplier for advice.
G
Gregory Anderson MDAug 27, 2025
What does overcurrent mean on a Danfoss VLT MCD 600?
Z
zrangelAug 27, 2025
If the Danfoss Controller shows an overcurrent, it means the current has exceeded the level set in parameter 5-5 for longer than the time set in parameter 5-6. This can be due to a momentary overload. Check the following parameters:
- Parameter 5-5 Overcurrent.
- Parameter 5-6 Overcurrent Delay.
- Parameter 6-5 Overcurrent.
M
Michael ConwayAug 26, 2025
What causes L1/L2/L3 phase loss in Danfoss Controller?
J
Julia MckayAug 26, 2025
If the Danfoss Controller detects a phase loss on L1, L2, or L3, it means that during pre-start checks, a phase loss was detected. In run state, it indicates that the current on the affected phase has dropped below 10% of the programmed motor FLC for more than 1 second, suggesting a loss of the incoming phase or a disconnection to the motor. Check the supply, input, and output connections for both the soft starter and the motor.
M
Mason GrayAug 25, 2025
How to resolve a motor overload error on a Danfoss VLT MCD 600 Controller?
C
caitlinspencerAug 26, 2025
If the motor has reached its maximum thermal capacity, the Danfoss Controller will show a motor overload. This can happen if the controller's protection settings don't match the motor's thermal capacity. Resolve the cause of the overload, allow the motor to cool down, and then check the following parameters:
- Parameter 1-2 Motor Full Load Current.
- Parameter 1-4 Locked Rotor Time.
- Parameter 1-5 Locked Rotor Current.
- Parameter 1-6 Motor Service Factor.
- Parameter 5-15 Excess Start Time.
- Parameter 6-10 Excess Start Time.