What does L1-T1/L2-T2/L3-T3 shorted mean on a Danfoss VLT MCD 600?
A
Anthony CooleyAug 31, 2025
If the Danfoss Controller detects L1-T1, L2-T2, or L3-T3 Shorted, it means that during pre-start checks, the soft starter has detected a short-circuited SCR or a short circuit within the bypass contactor. Consider using PowerThrough to allow operation until the soft starter can be repaired. Also, see parameter 6-19 Shorted SCR Action.
W
William BrownAug 31, 2025
What causes heat sink overtemperature on a Danfoss VLT MCD 600 Controller?
I
ian59Aug 31, 2025
If the Danfoss Controller displays a heat sink overtemperature warning, check the following:
- Ensure bypass contactors are operating.
- Verify cooling fans are functioning (MCD6-0064B~MCD6-0579B and MCD6-0042B~MCD6-0579B models).
- If in an enclosure, ensure adequate ventilation.
- Mount the VLT® Soft Starter MCD 600 vertically.
- Verify internal bypass contactors are operating using run simulation to measure resistance across each controlled phase (resistance should be >0.2 MΩ when open and
T
Theresa ParksSep 1, 2025
What to do for overvoltage error on Danfoss VLT MCD 600 Controller?
A
Alexander HayesSep 1, 2025
If the Danfoss Controller displays an overvoltage error, it indicates a voltage surge on the mains, possibly due to problems with a transformer tap regulator or off-loading of a large transformer load. Check the following parameters:
- Parameter 5-9 Overvoltage.
- Parameter 5-10 Overvoltage Delay.
- Parameter 6-7 Overvoltage.
A
Amanda TylerSep 1, 2025
What causes current imbalance in Danfoss VLT MCD 600 Controller?
J
Jacob BrooksSep 1, 2025
If the Danfoss Controller shows a current imbalance, it could be due to an imbalance in the incoming mains voltage, a problem with the motor windings, a light load on the motor, a phase loss on mains terminals L1, L2, or L3 during Run mode, or a failed SCR. Check the following parameters:
- Parameter 5-1 Current Imbalance.
- Parameter 5-2 Current Imbalance Delay.
- Parameter 6-3 Current Imbalance.
B
Blake LucasSep 2, 2025
What causes undercurrent on a Danfoss VLT MCD 600?
J
jeremy15Sep 2, 2025
If the Danfoss Controller displays an undercurrent, the motor has experienced a sharp drop in current, caused by loss of load. This can be due to broken components (shafts, belts, or couplings) or a pump running dry. Check the following parameters:
- Parameter 5-3 Undercurrent.
- Parameter 5-4 Undercurrent Delay.
- Parameter 6-4 Undercurrent.
B
Brian WarrenSep 2, 2025
What does underpower mean on Danfoss VLT MCD 600 Controller?
A
Andrea SimmonsSep 2, 2025
If the Danfoss Controller displays an underpower error, it means the motor has experienced a sharp drop in power, caused by loss of load. This can be due to broken components (shafts, belts, or couplings), or a pump running dry. Check the following parameters:
- Parameter 5-11 Underpower.
- Parameter 5-12 Underpower delay.
- Parameter 6-8 Underpower.
D
David DelacruzSep 4, 2025
How to troubleshoot motor connection T1/T2/T3 error on Danfoss Controller?
J
Jenna GloverSep 4, 2025
If the Danfoss Controller displays a 'Motor Connection T1/T2/T3' error, it means the motor is not connected correctly to the soft starter. Check individual motor connections to the soft starter for power circuit continuity and check connections at the motor terminal box. If the soft starter is connected to a grounded delta mains supply, adjust parameter 20-6 Motor Connection to match the motor connection configuration.
M
Mr. Craig JohnsonSep 16, 2025
What does internal fault X mean on Danfoss VLT MCD 600 Controller?