How to fix phase sequence error on Danfoss VLT MCD 600 Controller?
D
denisewoodAug 27, 2025
If the Danfoss Controller displays a phase sequence error, it means the phase sequence on the soft starter mains terminals (L1, L2, L3) is not valid. Check the phase sequence on L1, L2, and L3, and ensure that the setting in parameter 5-18 Phase Sequence is suitable for the installation.
C
Cynthia MillerAug 28, 2025
What causes undervoltage on a Danfoss VLT MCD 600?
J
Jessica MorganAug 28, 2025
If the Danfoss Controller is showing an undervoltage error, it means the mains voltage has dropped below the selected level. This can be caused by an undersized supply or adding a large load to the system. No solution was provided.
T
Thomas GarnerAug 28, 2025
What does motor thermistor error mean on Danfoss VLT MCD 600 Controller?
M
Mary FisherAug 28, 2025
If the Danfoss Controller displays a motor thermistor error, it means the motor thermistor input has been enabled and the resistance at the thermistor input has exceeded 3.6 kΩ for more than 1 second, or the motor winding has overheated. Identify the cause of the overheating and allow the motor to cool before restarting. Use the thermistor reset function to disable the thermistor. Check parameter 6-17 Motor Overtemperature.
K
Kerry TuckerAug 29, 2025
What to do if Danfoss VLT MCD 600 Controller shows a power loss error?
A
Alyssa FletcherAug 29, 2025
If the Danfoss Controller displays a power loss error, it means the soft starter is not receiving mains supply on one or more phases. Check that the main contactor closes when a start command is given and remains closed until the end of a soft stop. Also, check the fuses. If testing the soft starter with a small motor, it must draw at least 10% of the programmed FLC setting on each phase.
W
Walter LloydAug 30, 2025
What causes excess start time error on Danfoss Controller?
K
Kristen BakerAug 30, 2025
If the Danfoss Controller shows an excess start time error, possible causes are:
- Parameter 1-2 Motor Full Load Current is not appropriate for the motor.
- Parameter 2-4 Current Limit has been set too low.
- Parameter 2-2 Start Ramp Time has been set greater than the setting for parameter 5-15 Excess Start Time.
- Parameter 2-2 Start Ramp Time is set too short for a high inertia load when using adaptive control.
Check and adjust Parameter 1-2 Motor Full Load Current, Parameter 2-4 Current Limit, and Parameter 2-2 Start Ramp Time.
L
Lori JohnsonAug 30, 2025
What does L1-T1/L2-T2/L3-T3 shorted mean on a Danfoss VLT MCD 600?
A
Anthony CooleyAug 31, 2025
If the Danfoss Controller detects L1-T1, L2-T2, or L3-T3 Shorted, it means that during pre-start checks, the soft starter has detected a short-circuited SCR or a short circuit within the bypass contactor. Consider using PowerThrough to allow operation until the soft starter can be repaired. Also, see parameter 6-19 Shorted SCR Action.
J
Jason RobinsonAug 25, 2025
Why is my Danfoss Controller not ready?
I
Ian SmithAug 25, 2025
If the Danfoss Controller is not ready, the reset input may be active, preventing operation, or the soft starter may be waiting for the restart delay to elapse. Check the following parameters:
- Parameter 5-16 Restart Delay.
- Parameter 7-9 Reset/Enable Logic.
T
Theresa ParksSep 1, 2025
What to do for overvoltage error on Danfoss VLT MCD 600 Controller?
A
Alexander HayesSep 1, 2025
If the Danfoss Controller displays an overvoltage error, it indicates a voltage surge on the mains, possibly due to problems with a transformer tap regulator or off-loading of a large transformer load. Check the following parameters:
- Parameter 5-9 Overvoltage.
- Parameter 5-10 Overvoltage Delay.
- Parameter 6-7 Overvoltage.
A
Amanda TylerSep 1, 2025
What causes current imbalance in Danfoss VLT MCD 600 Controller?
J
Jacob BrooksSep 1, 2025
If the Danfoss Controller shows a current imbalance, it could be due to an imbalance in the incoming mains voltage, a problem with the motor windings, a light load on the motor, a phase loss on mains terminals L1, L2, or L3 during Run mode, or a failed SCR. Check the following parameters:
- Parameter 5-1 Current Imbalance.
- Parameter 5-2 Current Imbalance Delay.
- Parameter 6-3 Current Imbalance.
B
Blake LucasSep 2, 2025
What causes undercurrent on a Danfoss VLT MCD 600?
J
jeremy15Sep 2, 2025
If the Danfoss Controller displays an undercurrent, the motor has experienced a sharp drop in current, caused by loss of load. This can be due to broken components (shafts, belts, or couplings) or a pump running dry. Check the following parameters:
- Parameter 5-3 Undercurrent.
- Parameter 5-4 Undercurrent Delay.
- Parameter 6-4 Undercurrent.