What to do if Danfoss Controller shows SCR overtemperature?
T
thompsonjonathanSep 23, 2025
If the Danfoss Controller displays 'SCR Overtemperature', the temperature of the SCRs, calculated by the thermal model, is too high to allow further operation. Wait for the soft starter to cool.
A
Angel RogersSep 23, 2025
What does SCR Itsm mean on Danfoss VLT MCD 600?
N
Nancy MaynardSep 23, 2025
If the Danfoss Controller displays 'SCR Itsm', the SCR current surge rating has been exceeded. No solution was provided.
L
laurapotterSep 23, 2025
What causes RTD circuit error on Danfoss VLT MCD 600 Controller?
H
Heather WagnerSep 23, 2025
If the Danfoss Controller displays an RTD Circuit error, the smart card has detected a fault with the RTD sensor, or the RTD has activated temperature protection. Check the following parameters:
- Parameter 35-2 Temperature Trip Level.
- Parameter 36-10 RTD/PT100 B.
D
David JenkinsSep 23, 2025
How to fix starter communication error on Danfoss VLT MCD 600?
A
Ashley FreySep 23, 2025
If the Danfoss Controller displays a starter communication error, there is a problem with the connection between the soft starter and the optional communications module. Remove and reinstall the card. If the problem persists, contact the local distributor.
W
William BrownAug 31, 2025
What causes heat sink overtemperature on a Danfoss VLT MCD 600 Controller?
I
ian59Aug 31, 2025
If the Danfoss Controller displays a heat sink overtemperature warning, check the following:
- Ensure bypass contactors are operating.
- Verify cooling fans are functioning (MCD6-0064B~MCD6-0579B and MCD6-0042B~MCD6-0579B models).
- If in an enclosure, ensure adequate ventilation.
- Mount the VLT® Soft Starter MCD 600 vertically.
- Verify internal bypass contactors are operating using run simulation to measure resistance across each controlled phase (resistance should be >0.2 MΩ when open and
H
hbrennanAug 25, 2025
What to do if the Danfoss VLT MCD 600 Controller shows an instant overcurrent error?
K
Kimberly CooperAug 25, 2025
If the Danfoss Controller displays an instant overcurrent error, it means the current on all three phases has exceeded 7.2 times the value set for the motor's full load current. This could be due to a locked rotor or an electrical fault in the motor or cabling. Check for jammed loads and inspect the motor and cables for faults.
M
Mason GrayAug 25, 2025
How to resolve a motor overload error on a Danfoss VLT MCD 600 Controller?
C
caitlinspencerAug 26, 2025
If the motor has reached its maximum thermal capacity, the Danfoss Controller will show a motor overload. This can happen if the controller's protection settings don't match the motor's thermal capacity. Resolve the cause of the overload, allow the motor to cool down, and then check the following parameters:
- Parameter 1-2 Motor Full Load Current.
- Parameter 1-4 Locked Rotor Time.
- Parameter 1-5 Locked Rotor Current.
- Parameter 1-6 Motor Service Factor.
- Parameter 5-15 Excess Start Time.
- Parameter 6-10 Excess Start Time.
M
Michael ConwayAug 26, 2025
What causes L1/L2/L3 phase loss in Danfoss Controller?
J
Julia MckayAug 26, 2025
If the Danfoss Controller detects a phase loss on L1, L2, or L3, it means that during pre-start checks, a phase loss was detected. In run state, it indicates that the current on the affected phase has dropped below 10% of the programmed motor FLC for more than 1 second, suggesting a loss of the incoming phase or a disconnection to the motor. Check the supply, input, and output connections for both the soft starter and the motor.
G
Gregory Anderson MDAug 27, 2025
What does overcurrent mean on a Danfoss VLT MCD 600?
Z
zrangelAug 27, 2025
If the Danfoss Controller shows an overcurrent, it means the current has exceeded the level set in parameter 5-5 for longer than the time set in parameter 5-6. This can be due to a momentary overload. Check the following parameters:
- Parameter 5-5 Overcurrent.
- Parameter 5-6 Overcurrent Delay.
- Parameter 6-5 Overcurrent.
C
Calvin ClaytonAug 27, 2025
Why does my Danfoss VLT MCD 600 Controller show a frequency error?
D
Donald DelgadoAug 27, 2025
If the Danfoss Controller shows a frequency error, the mains frequency is outside the specified range. This issue is not adjustable. Check for other equipment that could be affecting the mains supply, especially drives and switch mode power supplies. If the soft starter is connected to a generator set supply, the generator may be too small or have a speed control problem. Check parameter 6-15 Frequency.