What does underpower mean on Danfoss VLT MCD 600 Controller?
A
Andrea SimmonsSep 2, 2025
If the Danfoss Controller displays an underpower error, it means the motor has experienced a sharp drop in power, caused by loss of load. This can be due to broken components (shafts, belts, or couplings), or a pump running dry. Check the following parameters:
- Parameter 5-11 Underpower.
- Parameter 5-12 Underpower delay.
- Parameter 6-8 Underpower.
B
Barbara ColemanSep 3, 2025
What to do if Danfoss Controller detects low control volts?
M
Mary ParkerSep 3, 2025
If the Danfoss Controller detects low control volts, it means the soft starter has detected a drop in the internal control voltage. This protection is not active in ready state. Check the external control supply (terminals A7, A8, A9) and reset the soft starter. If the external control supply is stable, check if the 24 V supply on the main control PCB is faulty, or check if the bypass driver PCB is faulty. Contact the local supplier for advice.
D
David DelacruzSep 4, 2025
How to troubleshoot motor connection T1/T2/T3 error on Danfoss Controller?
J
Jenna GloverSep 4, 2025
If the Danfoss Controller displays a 'Motor Connection T1/T2/T3' error, it means the motor is not connected correctly to the soft starter. Check individual motor connections to the soft starter for power circuit continuity and check connections at the motor terminal box. If the soft starter is connected to a grounded delta mains supply, adjust parameter 20-6 Motor Connection to match the motor connection configuration.
A
Ashley JohnsonSep 4, 2025
What does 'starts per hour' mean on Danfoss Controller?
M
Martin Perry Jr.Sep 5, 2025
If the Danfoss Controller indicates 'Starts per Hour', it means the soft starter has already attempted the maximum number of starts in the last 60 minutes. Wait before attempting another start. To determine when the waiting period ends, review the log.
D
Deborah HunterSep 5, 2025
What causes overpower error on Danfoss Controller?
C
Catherine MitchellSep 5, 2025
If the Danfoss Controller displays an overpower error, it means the motor has experienced a sharp rise in power, possibly due to a momentary overload. Check the following parameters:
- Parameter 5-13 Overpower.
- Parameter 5-14 Overpower Delay.
- Parameter 6-9 Overpower.
S
Stanley BradySep 6, 2025
What to do if Danfoss Controller shows Battery/Clock error?
M
Michaela JamesSep 6, 2025
If the Danfoss Controller shows a Battery/Clock error, a verification error has occurred on the real-time clock, or the back-up battery voltage is low. If the battery is low and the power is off, date/time settings are lost. Reprogram the date and time. The battery is not removable; to replace it, the main control PCB must be replaced. Check parameter 6-20 Battery Clock.
O
osbornmarissaSep 6, 2025
How to troubleshoot 2-phase-damaged SCR on Danfoss VLT MCD 600 Controller?
F
Francisco SanchezSep 6, 2025
If the Danfoss Controller indicates a 2-Phase-damaged SCR, check for either a shorted SCR or a short within the bypass contactor. Also, check parameter 6-19 Shorted SCR Action.
M
Mrs. Meredith ConnerSep 7, 2025
What causes firing fail Px on Danfoss Controller?
M
matthew76Sep 7, 2025
If the Danfoss Controller displays 'Firing Fail Px', it means the SCR did not fire as expected. Check for faulty SCRs and internal wiring faults.