EasyManuals Logo

Danfoss VLT Micro Drive FC 51 Programming Guide

Danfoss VLT Micro Drive FC 51
72 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #14 background imageLoading...
Page #14 background image
4.1.3 0-5* Copy/Save
0-50 LCP Copy
Option: Function:
The detachable LCP of the frequency
converter
can be used for storing setups,
and thus for transferring data when
moving parameter settings from one
frequency converter to another.
NOTE
LCP Copy can only be activated from
the LCP and ONLY when the motor
is coasted.
[1] All to LCP Copy all setups from the frequency
converter
into the LCP.
[2] All from LCP Copy all setups from LCP to frequency
converter.
[3] Size independent
from
LCP
Copy non motor size dependent data
from LCP to frequency converter.
0-51 Set-up Copy
Option: Function:
Use this function to copy a set-up content
into
the Edit Set-up.
In order to be able to make a set-up copy
ensure that
the motor is coasted
0-10 Active Set-up, Active Set-up, is
set to either [1] Set-up 1 or [2] Set-
up 2
NOTE
The keyboard/parameter database are
blocked while Set-up Copy is running.
[0 ] * No Copy Copy function is inactive
[1] Copy from
Set-up
1
Copy from Set-up 1 to edit set-up chosen in
0-11 Edit Set-up.
[2] Copy from
Set-up
2
Copy from Set-up 2 to edit set-up chosen in
0-11 Edit Set-up.
[9] Copy from
Factory
Set-
up
Copy from Factory Settings to edit set-up
chosen in 0-11 Edit set-up.
4.1.4 0-6* Password
0-60 (Main) Menu Password
Range: Function:
Use password for protection against unintended
change
of sensitive parameters, eg. motor
parameters.
0 * [0-999] Enter the password for access to Main Menu via
the
[Main Menu] key. Select the number that
should allow for changing other parameter values.
0 means there is no password.
NOTE
A password has affect on the LCP - not on the bus
communication.
NOTE
Pressing
[Menu], [OK] and [
] will unlock the password.
This will automatically enter the parameter editing screen
in Quick Menu or Main Menu.
0-61 Access to Main/Quick Menu w/o Password
Option: Function:
[0] * Full access
Select [0] Full Access to disable the
password in 0-60 (Main) Menu Password.
[1] LCP: Read Only
Select [1]
Read Only to block unauthorized
editing of Main/Quick menu parameter.
[2] LCP: No Access
Select [2]
No Access to block unauthorized
editing and viewing of Main/Quick menu
parameter.
Parameter Descriptions
VLT
®
Micro Drive FC 51 Programming Guide
MG02C602 - VLT
®
is a registered Danfoss trademark
13
4 4
RSPSupply - 1-888-532-2706 - www.RSPSupply.com
http://www.RSPSupply.com/p-12769-Danfoss-132F0026-VFD-Micro-Drive-440V-5HP.aspx

Other manuals for Danfoss VLT Micro Drive FC 51

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT Micro Drive FC 51 and is the answer not in the manual?

Danfoss VLT Micro Drive FC 51 Specifications

General IconGeneral
EnclosureIP20
Output Voltage0-100% of supply voltage
AltitudeUp to 1000 m without derating
Power Range0.18-22 kW
Control MethodV/f
CommunicationModbus RTU
Protection FeaturesOver-voltage, under-voltage, over-current, over-temperature
Ambient Temperature-10°C to 50°C
Storage Temperature-25°C to 65°C
Relative Humidity5-95% (non-condensing)
Input Voltage200-240 V, 380-480 V
Braking FunctionIntegrated braking chopper (optional)

Related product manuals