1 Safety
1.1.1 High Voltage Warning
WARNING
The voltage of the frequency converter is dangerous
whenever
it is connected to mains. Incorrect installation of
the motor or frequency converter may cause damage to
the equipment, serious injury or death. Consequently, it is
essential to comply with the instructions in this manual as
well as local and national rules and safety regulations.
1.1.2 Safety Instructions
CAUTION
Before
using functions directly or indirectly influencing
personal safety (e.g. Safe Stop, Fire Mode or other
functions either forcing the motor to stop or attempting to
keep it functioning) a thorough risk analysis and system
test must be carried through. The system tests must
include testing failure modes regarding the control
signaling (analog and digital signals and serial communi-
cation.
NOTE
Before
using Fire Mode, contact Danfoss
Make
sure the frequency converter is properly
connected to earth.
Do not remove mains connections, motor
connections or other power connections while
the frequency converter is connected to power.
Protect users against supply voltage.
Protect the motor against overloading according
to national and local regulations.
The earth leakage current exceeds 3.5 mA.
The [Off] key is not a safety switch. It does not
disconnect the frequency converter from mains.
1.1.3 Software Version and Approvals
Software Version
Programming
Guide
VLT
®
Micro Drive
FC 51 Series
This Programming Guide can be used for all VLT
®
Micro
Drive frequency converters with software
version 2.7X.
The software version number can be read in
15-43 Software Version.
Table 1.1
1.1.4 General Warning
WARNING
ELECTRICAL SHOCK HAZARD
Touching
the electrical parts may be fatal - even after the
equipment has been disconnected from mains.
Also make sure that other voltage inputs have been
disconnected (linkage of DC intermediate circuit).
Be aware that there may be high voltage on the DC link
even when the LEDs are turned off.
Before touching any potentially live parts of the frequency
converter, wait at least 4 min for all sizes.
Shorter time is allowed only if indicated on the nameplate
for the specific unit.
Safety
VLT
®
Micro Drive FC 51 Programming Guide
MG02C602 - VLT
®
is a registered Danfoss trademark
3
1 1
RSPSupply - 1-888-532-2706 - www.RSPSupply.com
http://www.RSPSupply.com/p-12769-Danfoss-132F0026-VFD-Micro-Drive-440V-5HP.aspx

Other manuals for Danfoss VLT Micro Drive FC 51

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT Micro Drive FC 51 and is the answer not in the manual?

Danfoss VLT Micro Drive FC 51 Specifications

General IconGeneral
EnclosureIP20
Output Voltage0-100% of supply voltage
AltitudeUp to 1000 m without derating
Power Range0.18-22 kW
Control MethodV/f
CommunicationModbus RTU
Protection FeaturesOver-voltage, under-voltage, over-current, over-temperature
Ambient Temperature-10°C to 50°C
Storage Temperature-25°C to 65°C
Relative Humidity5-95% (non-condensing)
Input Voltage200-240 V, 380-480 V
Braking FunctionIntegrated braking chopper (optional)