2-17 Over-Voltage Control
Option: Function:
Use Over-voltage Control (OVC) to reduce
the
risk of the frequency converter tripping
due to an over voltage on the DC link
caused by generative power from the load.
An over-voltage occurs eg. if the ramp down
time is set too short compared to the actual
load inertia.
[0] * Disabled The OVC is not active/required.
[1] Enabled, not
at
stop
OVC is running unless a stop signal is active.
[2] Enabled OVC is running, also when a stop signal is
active.
NOTE
If
Resistor Brake has been chosen in 2-10 Brake Function
the OVC is not active even though enabled in this
parameter.
4.3.4 2-2* Mechanical Brake
For hoisting applications an electro-magnetic brake is
required.
The brake is controlled by a relay, which releases
the brake when activated.
The brake activates if the frequency converter trips or a
coast command is given. Furthermore, it activates when
motor speed is ramped down below the speed set in 2-22
Active Brake Speed.
2-20 Release Brake Current
Range: Function:
0.00 A* [0.00-100 A] Select motor current at which mechanical
brake
releases.
CAUTION
If start delay time has passed, and
motor
current is below Release brake
current, frequency converter trips.
2-22 Activating Mechanical Brake
Range: Function:
If the motor is stopped using ramp, the
mechanical
brake is activated when motor
speed is less than Active Brake Speed.
Motor is ramped down to stop in the following
situations:
A start command is removed (stand
by)
A stop command is activated
Quick-stop is activated (Q-stop ramp is
used)
0 Hz* [0-400
Hz]
Select motor speed at which mechanical brake
activates
when ramping down.
Mechanical brake automatically activates if
frequency converter trips or reports an alarm.
Parameter Descriptions
VLT
®
Micro Drive FC 51 Programming Guide
20 MG02C602 - VLT
®
is a registered Danfoss trademark
44
RSPSupply - 1-888-532-2706 - www.RSPSupply.com
http://www.RSPSupply.com/p-12769-Danfoss-132F0026-VFD-Micro-Drive-440V-5HP.aspx

Other manuals for Danfoss VLT Micro Drive FC 51

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT Micro Drive FC 51 and is the answer not in the manual?

Danfoss VLT Micro Drive FC 51 Specifications

General IconGeneral
EnclosureIP20
Output Voltage0-100% of supply voltage
AltitudeUp to 1000 m without derating
Power Range0.18-22 kW
Control MethodV/f
CommunicationModbus RTU
Protection FeaturesOver-voltage, under-voltage, over-current, over-temperature
Ambient Temperature-10°C to 50°C
Storage Temperature-25°C to 65°C
Relative Humidity5-95% (non-condensing)
Input Voltage200-240 V, 380-480 V
Braking FunctionIntegrated braking chopper (optional)