EasyManuals Logo

Danfoss VLT Micro Drive FC 51 Programming Guide

Danfoss VLT Micro Drive FC 51
72 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #36 background imageLoading...
Page #36 background image
130BD020.10
(mA)
0%
20
0/4
100%
Current
Analogue
output
Min Scale
par. 6-93
Variable
for
output
example:
Speed
(RPM)
Analogue
Output
Max Scale
par. 6-94
Illustration 4.9
6-94 Terminal 42 Output Max. Scale
Range: Function:
100.00%*
[0.00-200.00%]
Scale maximum output of selected
analog
signal at terminal 42. Set value
to maximum value of current signal
output. Scale output to give a current
lower than 20 mA at full scale; or 20
mA at an output below 100% of
maximum signal value.
If 20 mA is the desired output current
at a value between 0-100% of the full-
scale output, programme percentage
value in the parameter, i.e. 50% = 20
mA. If a current between 4 and 20
mA is desired at maximum output
(100%), calculate percentage value as
follows:
20
mA
desired
maximum
current
× 100 %
i.e.
10
mA
=
20
10
× 100 =
200 %
Parameter Descriptions
VLT
®
Micro Drive FC 51 Programming Guide
MG02C602 - VLT
®
is a registered Danfoss trademark
35
4 4
RSPSupply - 1-888-532-2706 - www.RSPSupply.com
http://www.RSPSupply.com/p-12769-Danfoss-132F0026-VFD-Micro-Drive-440V-5HP.aspx

Other manuals for Danfoss VLT Micro Drive FC 51

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT Micro Drive FC 51 and is the answer not in the manual?

Danfoss VLT Micro Drive FC 51 Specifications

General IconGeneral
EnclosureIP20
Output Voltage0-100% of supply voltage
AltitudeUp to 1000 m without derating
Power Range0.18-22 kW
Control MethodV/f
CommunicationModbus RTU
Protection FeaturesOver-voltage, under-voltage, over-current, over-temperature
Ambient Temperature-10°C to 50°C
Storage Temperature-25°C to 65°C
Relative Humidity5-95% (non-condensing)
Input Voltage200-240 V, 380-480 V
Braking FunctionIntegrated braking chopper (optional)