14-22 Operation Mode
Option: Function:
14-22 Operation Mode
also reverts to default
setting [0] Normal Operation.
14-26 Action at Inverter Fault
Option: Function:
[0] Trip When the frequency converter detects an over-
voltage,
it will trip immediately.
NOTE
It is recommended to choose [0] Trip in
hoisting applications.
[1] * Warning When the frequency converter detects an over-
voltage, it will give warning immediately. After
protection filter, it will trip.
NOTE
It is recommended to disable protection
mode in hoisting applications.
4.11.4 15-4* Drive Identification
Parameters containing read only information about the
hardware
and software configuration of the frequency
converter.
14-41 AEO Minimum Magnetization
Range: Function:
66%* [40-75%] Enter the minimum allowable magnetization
for
AEO. Selecting a low value reduces energy
loss in the motor, but may also reduce
resistance to sudden load changes.
Parameter Descriptions
VLT
®
Micro Drive FC 51 Programming Guide
46 MG02C602 - VLT
®
is a registered Danfoss trademark
44
RSPSupply - 1-888-532-2706 - www.RSPSupply.com
http://www.RSPSupply.com/p-12769-Danfoss-132F0026-VFD-Micro-Drive-440V-5HP.aspx

Other manuals for Danfoss VLT Micro Drive FC 51

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT Micro Drive FC 51 and is the answer not in the manual?

Danfoss VLT Micro Drive FC 51 Specifications

General IconGeneral
EnclosureIP20
Output Voltage0-100% of supply voltage
AltitudeUp to 1000 m without derating
Power Range0.18-22 kW
Control MethodV/f
CommunicationModbus RTU
Protection FeaturesOver-voltage, under-voltage, over-current, over-temperature
Ambient Temperature-10°C to 50°C
Storage Temperature-25°C to 65°C
Relative Humidity5-95% (non-condensing)
Input Voltage200-240 V, 380-480 V
Braking FunctionIntegrated braking chopper (optional)