VLT
®
2800 Series
Programming
If the frequency converter d isplays a fault code from
37-45, the control card test has failed. Cha nge the
control card to start up the frequency converter.
If the frequenc y converter comes into Display mode,
the test is OK. Remove the test connector and
the frequency converter is ready for operation.
Parameter 620 Operating mode is automatically
set to Normal operation [0].
Initialisation [3] is selected if you wish to use
the unit’sfactorysetting.
Procedure for initialisation:
1. Select Initialisation [3].
2. Disconnect the mains voltage and wait until the
light in the display has disappeared.
3. Connect the mains voltage.
4. An init ialisation is performed in all parameters
in all Setups, with the exception of parameters
500 Address, 501 Baudrate, 600-605 Operating
data and 615-617 Fault log.
✭ = factory setting. () = di splay text [] = value for use in communication via serial communicat ion port
MG.28.E9.02 - VLT is a registered Danfoss trademark
129