VLT
®
2800 Series
Programming
Shifting from Remote control to Loc al control in
parameter 002 Local/remote operation,whilethis
parameter has been set to Remote-operated control
as parameter 100 [4]: the p resent reference will
be maintained. If the reference signal is negat ive,
thelocalreferencewillbesetto0.
Shifting from Local operation to Remote operation
in parameter 002 Local/remote operation, while
this parameter has been set to Remote operation:
The local reference will be repla ced by the
remote-operated reference signal.
014 Local stop
(LOCAL STOP)
Value:
Not active ( DISABLE)
[0]
✭Active (ENABLE)
[1]
Function:
In this parameter, the local [STOP]-key can be
engaged or disengaged on the control panel
and on the LCP control panel.
Description of choice:
If Not active [0] is selected in this parameter,
the [STOP]-key will be inactive.
NB!:
If Not active [0] is selected, the motor cannot
be stopped by means of the [STOP]-key.
015 Local jog
(LOCAL JOGGING)
Value:
✭Not act ive (DISABLE)
[0]
Active (ENABLE)
[1]
Function:
In this parameter, the jog function on the LCP
control panel can be engaged/disengaged.
Description of choice:
If Not active [0] is selected in this parameter,
the [JOG]-key will be inactive.
016 Local reversing
(LOCAL REVERSING)
Value:
✭Not active ( DISABLE)
[0]
Active (ENABLE)
[1]
Function:
In this parameter you can select/deselect the reversing
function o n the LCP control p anel. The key can only
be used if parameter 002 Local/remote operation
is set to Local operation [1] and parameter 013
Localcontrol to Local control, open loop [1] or
Local control as parameter 100 [3].
Description of choice:
If Disable [0] is selected in this parameter, the
[FWD/REV] key will be disabled. See also parameter
200 Output frequency range.
017 Local reset of trip
(LOCAL RESET)
Value:
Not active (DISABLE)
[0]
✭Active (ENABLE)
[1]
Function:
In this parameter, the reset funct ion on the control
panel can be engag ed/disengaged.
Description of choice:
If Not active [0] is selected in this parameter,
the reset function will be inactive.
NB!:
Select Not active [0], only if an external reset
signal has been connected via the digital inputs.
018 Lock for data changes
(DATA CHANGE LOCK)
Value:
✭Not locked ( N O T LOCKED)
[0]
Locked ( LOCKED)
[1]
Function:
In this parameter, it is possible to ’lock’ the controls
to disable data changes via the control keys.
Description of choice:
If Locked [1] is selected, data changes in the
parameters cannot be made; however, it will
stillbepossibletomakedatachangesviaserial
✭
= factory setting. () = display text [] = value for use in communication via serial communication port
MG.28.E9.02 - VLT is a registered Danfoss trademark
65