VLT
®
2800 Series
communication. P arameter 009-012 D isplay readout
can be changed via the control panel.
019 Operating mode at power-up, local
operation
(POWER UP ACTION)
Value:
Auto restart, use saved reference
(AUTO RESTART)
[0]
Forced s top, use saved reference
(LOCAL=STOP)
[1]
Forced stop, set ref. to 0
(LOCAL=STOP, REF=0)
[2]
Function:
Setting of the required operat ing mode when the
mains voltage is en gaged. This fu nction can only
be active if Local operation [1] has been selected
in parameter 002 Local/remote operation.
Description of choice:
Auto restart, use saved ref. [0] is selected if the
frequency converter is to start using the local reference
(set in parameter 003 Local reference)andthe
start/stop state given via the control keys immediately
prior to the mains voltage b eing cut out.
Forced stop, use saved ref. [1] is selected if the
frequency converter is to remain stopped when the
mains voltage is engaged, until the [START]-key
is activated. After a start command the motor
speed is ramped up to the saved reference in
parameter 003 Local reference.
Forced stop, set ref. to 0 [2] is selected if the
frequency converter is to remain stopped when
the mains voltage is cut back in. Parameter 003
Local reference is to be zeroed.
NB!:
In remote operat ion (parameter 002
Local/remote operation) the start/stop state
at the time of mains connection will depend
on the external control signals. If Pulse start [8] is
selected in parameter 302 Digital input,themotor
will remain stopped after mains connection.
020 Hand operation
(HAND OPERATION)
Value:
Not act ive (DISABLE)
[0]
Active (ENABLE)
[1]
Function:
In this parameter you can select whether it s hould
be possible or not to switch between Auto- and
Hand mode. In Auto mode the frequency converter is
controlled by external signals whereas the frequency
converter in Hand mode is controlled via a local
reference directly from the control unit.
Description of choice:
If Not a ctive [0] is selected in this parameter, the Hand
mode function will be inactive. If Active [1] is selected
you can switch between Auto- and Ha nd mode. For
further informat ion, see the Control Unit section.
024 Userdefined Quick Menu
(USER QUICKMENU)
Value:
Not active ( DISABLE)
[0]
Active (ENABLE)
[1]
Function:
In this parameter you can select the standard
setup of the Quick menu key on the control
panel and the LCP 2 control panel.
Using this function, in parameter 025 Quick Menu
setup the user can select up to 20 parameters
for the Quick Menu key.
Description of choice:
If not active [0] is selected, the standard setup
of the Quick M e nu key is active.
If Active [1] is selected, the user-defined
Quick Menu is active.
025 Quick Menu setup
(QUICK MENU SETUP)
Value:
[Index 1 - 20] Value: 0 - 999
000
Function:
In this parameter you define w hich parameters are
required in the Quick Menu when parameter 024
User-defined Quick Menu is set to Active [1]
´
.
Up to 20 parameters can be selected for the
user-defined Quick Menu.
NB!:
Please note that this parameter can only be set
using an LCP 2 control panel. See Order form.
= factory setting. () = display text [] = value for use in communication via serial communication port
MG.28.E9.02 - VLT is a registered Danfoss trademark
66