Electrical data, connections and wiring
Fuses / circuit breakers
Frequency converter
EN50178
compliant fuses
UL Compliant fuses Recommended circuit breaker
Bussmann SIBA Little fuse IP20 IP55
Size Type Type RK1 Type J Type T Type RK1 Type RK1 Type RK1 Moeller type
200-240 V
CDS-15kW 125 A gG KTN-R125 JKS-150 JJN-125 2028220-125 KLN-R125 A2K-125R NZMB1-A100 NZMB2-A200
CDS-18.5 kW 125 A gG K TN-R125 JKS-150 JJN-125 2028220-125 KLN-R125 A2K-125R NZMB2-A200 NZMB2-A200
CDS-22 kW 160 A gG FWX-150 - - 2028220-150 L25S-150 A25X-150 NZMB2-A200 NZMB2-A200
380-480 V
CDS-15 kW 63 A gG KTS-R50 JKS-50 JJS-50 5014006-050 KLS-R50 A6K-50R PKZM4-50 PKZM4-63
CDS-18.5 Kw 63 A gG KTS-R60 JKS-60 JJS-60 5014006 -063 KLS-R60 A6K-60R NZMB1-A100 NZMB1-A100
CDS-22 kW 80 A gG KTS-R80 JKS-80 JJS-80 2028220-100 KLS-R80 A6K-80R NZMB1-A100 NZMB1-A100
525-600V
CDS-18.5 kW 40A gG KTS-R50 JKS-50 JJS-50 5014006-050 KLS-R50 A6K-50R NZMB1-A100 -
CDS-30 kW 63A gG KTS-R80 JKS-80 IJS-80 5014006-080 KLS-R80 A6K-80R NZMB1-A100 -
Danfoss recommends using the fuses/circuit
breakers listed below to protect service
personnel and property in case of component
break-down in the frequency converter. For
circuit breakers, Moeller types have been tested
and are recommended. Other types of circuit
breakers may be used provided they limit the
energy to a level equal to or lower than the
Moeller types.
35FRCC.PC.023.A8.02
Application Guidelines

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VZH088-G single and is the answer not in the manual?

Danfoss VZH088-G single Specifications

General IconGeneral
BrandDanfoss
ModelVZH088-G single
CategoryAir Compressor
LanguageEnglish

Related product manuals