34
MENU - Press MENU button to view next sub-menu
Display will read: 4-7 LOW DISCHARGE TEMP ALARM LIMIT
SELECT or - Press SELECT button to view current setting
Display will read: 4-7 LOW DISCHARGE TEMP ALARM LIMIT
SET AT: nnF (C)
NOTE: Low discharge temperature alarm limit requires an optional discharge air sensor.
Sensor is factory installed if ordered with unit. If sensor is not installed, the following
message will be displayed:
SENSOR NOT INSTALLED ON THIS UNIT
If sensor is installed the temperature alarm limit has a range of 45 to 60ºF (7.2
to 15.6ºC). Low discharge temperature alarm can also be disabled through Sub-
Menu 4-7. If disabled, the following message will displayed:
DISABLE LOW DISCHARGE TEMP ALARM
SELECT or - To change current setting
Factory setting is: 52º F (C)
MENU - To view next sub-menu
Display will read: 4-8 COMPRESSOR SHORT-CYCLE ALARM
SELECT or - To view current setting
Display will read: 4-8 COMPRESSOR SHORT-CYCLE ALARM
COMPRESSOR SHORT-CYCLE ALARM: ON
SELECT or - To change current setting
NOTE: There are two settings available ON or OFF. A compressor short-cycle alarm will
activate if the compressor has been energized ten (10) times in a one (1) hour period.
Compressor life can be shortened by allowing frequent cycling. On-going short-cycle
alarm problems should be analyzed before selecting “OFF.”
Factory setting is: ON
MENU - To view next sub-menu
Display will read: 4-9 WATER UNDER FLOOR ALARM ACTION
SELECT or - To view current setting
Display will read: 4-9 WATER UNDER FLOOR ALARM ACTION
ACTION: aaaa
There are three available selections:
NONE - Audio alarm only.