COMPRESSOR SHORT-CYCLE ALARM
1. The alarm is programmed (ON or OFF) through sub-menu 4-8. A compressor short-cycle alarm will activate if the
compressor has been energized ten (10) times in a one(1) hour period
2. The alarm is a warning only. Compressor operation will continue.
3. One cycle is a combination of compressor starts for cooling or dehumidi cation functions.
4. If the compressor is started 10 times in a one (1) hour period, the alarm will be activated and the message
COMPRESSOR SHORT-CYCLE” will be displayed on the processor display.
5. The compressor short-cycle time delay will be increased from ve (5) to six (6) minutes for the next hour.
6. The short-cycle alarm will not clear until a one (1) hour period has passed with less than ten (10) compressor starts.
POWER PROBLEM OR RESTART MODE
The power problem or restart mode is programmed through sub-menu 3-10. There are three selections available:
1. AUTOMATIC: NO MESSAGE OR ALARM – The unit will automatically start after a power failure or reset. No audio
alarm will sound. No message will be displayed on the processor display screen.
2. AUTOMATIC: MESSAGE, AUDIO ALARM & RELAY – The unit will automatically restart after a power failure or
reset. The audio alarm will be activated and the message “POWER FAILURE RESTART” will be displayed on the
processor display screen. Pressing the “SILENCE” button (when the message appears on the processor display
screen) will clear the alarm. The alarm will also clear itself ve (5) minutes if there is no button activity.
3. MANUAL: MESSAGE, AUDIO ALARM & RELAY – The unit will NOT automatically restart after a power failure or
reset. The “SILENCE” button must be pressed to restart the unit. The audio alarm will be activated and the message
POWER FAILURE RESTART” will be display on the processor display screen.
NO AIRFLOW ALARM
1. When no air ow is detected via the air ow switch, the cooling, reheat humidi cation and dehumidi cation functions
are locked out until the alarm condition is corrected. Sub-menu 4-24 allows you to adjust the delay the polling of the
air ow detector at start-up of the fan from 5 to 180 seconds. This is to minimize false alarms due to air turbulence.
2. The audio alarm is activated and ‘NO AIRFLOW” message will be displayed on the processor display screen.
DIRTY FILTER ALARM
When a dirty lter is detected, using a pressure differential switch, the audio alarm is activated and a “DIRTY FILTER:
CHECK FILTERS” message will be displayed on the processor display screen until the alarm condition has been
corrected.
HUMIDIFIER FAILURE: CHECK WATER PRESSURE SWITCH
1. On units with humidi ers an audio alarm is activated and “HUMIDIFIER FAILURE – CHECK WATER PRESSURE
message will be displayed on the processor screen if the humidi er water pressure switch does not sense adequate
supply water pressure.
2. The alarm will prevent the humidi er from operating until the alarm is corrected.

Other manuals for Data Aire DAP III

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Data Aire DAP III and is the answer not in the manual?

Data Aire DAP III Specifications

General IconGeneral
BrandData Aire
ModelDAP III
CategorySecurity System
LanguageEnglish

Related product manuals