D-200 MK2 User Manual Firmware V-6.3
L058D01-EN - 73 -
0: no MODEM / no GPS
1: Internal MODEM, no GPS
2: External Datakom MODEM, no GPS
3: External generic MODEM, no GPS
4: no MODEM, RS-232 GPS
5: Internal MODEM, RS-232 GPS
This is the data rate of the RS-232 port
for the external modem / GPS.
If the GSM SIM card uses pin number,
enter the pin number here. If incorrect
pin number is entered, then the SIM card
will not operate.
0: SMS messages disabled
1: SMS messages enabled
0: GPRS disabled
1: GPRS enabled
Rainbow Scada Refresh
Rate
The unit will update the distant
monitoring terminal with this rate.
Rainbow Scada
Address-1 Port
This is the port number of the first
monitoring terminal address.
Rainbow Scada
Address-2 Port
This is the port number of the second
monitoring terminal address.
0: RS-485 port disabled
1: RS-485 port enabled
This is the modbus controller identity
used in Modbus communication.
Oil Pressure Switch
Priority
0: crank cut is performed through oil
pressure switch and oil pressure sender
reading
1: crank cut is performed only through oil
pressure switch
Delayed Simulate Mains Operation:
max genset running time after Simulate
Mains signal disappears.
Dual Genset Systems: flashing relay ON
state duration timer.
Dual Genset Systems: flashing relay
OFF state duration.
This parameter trims precisely the real
time clock circuit. Values from 0 to 63
speed up the clock with 0.25sec/day
steps. Values from 127 to 64 slow down
the clock with 0.25sec/day steps.
This parameter provides the mains and
genset voltage limits with a hysteresis
feature in order to prevent faulty
decisions.
For example, when the mains are
present, the mains voltage low limit will
be used as the programmed low limit.
When the mains fail, the low limit will be
incremented by this value. It is advised
to set this value to 8 volts.
16.1. CONTROLLER CONFIGURATION GROUP (continued)