0: Genset control
1: Engine control (no alternator)
This parameter is used for frequency to
rpm conversion. For a 1500/1800 rpm
engine select 2. For a 3000/3600 rpm
engine select 1.
RPM from genset
frequency
0: read rpm from the MPU input
1: convert frequency to rpm (using
Alternator Pole Pairs)
This is the number of pulses generated
by the magnetic pickup sensing unit in
one turn of the flywheel.
This parameter controls SMS sending
when mains voltages status is changed.
No warnings generated.
0: no SMS on mains failed or restored
1: SMS sent on mains failed or restored
This parameter controls SMS sending
when IP address of GPRS connection is
changed. No warnings generated.
0: no SMS on IP change
1: SMS sent on IP change
This parameter controls e-mail sending
when IP address of GPRS or ethernet
connection is changed. No warnings
generated.
0: no e-mail on IP change
1: e-mail sent on IP change
If the fuel level measured from the
sender input falls below this level, then
the FUEL PUMP function will become
active.
If the fuel level measured from the
sender input goes above this level, then
the FUEL PUMP function will become
passive.
This parameter controls the activation of
the ALARM output during “Engine Start
Delay” timer before engine run.
0: no warning before start
1: warning before start
0: warnings are latching/non-latching on
parameter control
1: all warnings are latched. Even if the
fault source is removed, warnings will
persist until manually reset.
This parameter controls remote control
of the unit through Rainbow, Modbus
and Modbus TCP/IP.
0: remote control disabled
1: remote control enabled