DK-40 USER MANUAL V2.6 (02.08.2011)
K13D01-E - 27 -
No Description Adjustment Range Factory set
P40 RL5 function selection
0: Alarm
1: Fan
2: Load
3: No load
4: Motor run
5: Motor stopped
Refer chapter 8 for more details.
2
P41 Fan On Temperature (RL5)
30 ... (P09-2)
Refer chapter 8 for more details.
85 °C
P42
Delta T Fan Off
Temperature (RL5)
5 ... 15
Refer chapter 8 for more details.
10 °C
P43 Reserved - 0
P44 Reserved - 0
P45
Pressure loss preventing
method
0: standard operation
1: step increase/decrease
2: dynamic calculation
0
P46 Reserved - 0
P47 Reserved - 0
P48 Connection topology
1: 1 phase
2: 2 phases
3: 3 phases
3
P49 Phase L1 calibration 1 ...32767 1186
P50 Phase L2 calibration 1 ... 32767 1186
P51 Phase L3 calibration 1 ... 32767 1186
P52
Low Frequency Alarm
Enable
0: Disable
1: Enable
If this parameter is set to 0, the
P53 parameter will not be
displayed.
1
P53 Low Frequency Alarm Limit 10.0 ... 60.0 Hz 48.0 Hz
P54
High Frequency Alarm
Enable
0: Disable
1: Enable
If this parameter is set to 0, the
P55 parameter will not be
displayed.
1