DK-40 USER MANUAL V2.6 (02.08.2011)
K13D01-E - 28 -
No Description Adjustment Range Factory set
P55
High Frequency Alarm
Value
60.0 ... 990.0 Hz 62.0 Hz
P56 Frequency display
0: Disable
1: Enable
1
P57 Phase L1 voltage display
0:Disable
1:Enable
0
P58 Phase L2 voltage display
0:Disable
1:Enable
0
P59 Phase L3 voltage display
0:Disable
1:Enable
0
P60 Phase L1-L2 voltage display
0:Disable
1:Enable
1
P61 Phase L2-L3 voltage display
0:Disable
1:Enable
1
P62 Phase L3-L1 voltage display
0:Disable
1:Enable
1
P63 MODBUS enable
0: Disable
1: Enable
1
P64 Master/Slave MODBUS
0: Slave
1: Master
0
P65 MODBUS node address
1: Starts multiple controller opr.
2 ... 254: Modbus address
240
P66
Slave Start Timer (Multiple
controller operation)
1..999 sec. 180 sec
P67
Master Change Period
(Multiple operation)
1..999 hours 100 hours
P68 Serial Number Low Word 0 ... 65535 10
P69 Serial Number High Word 0 ... 65535 10
P70 High Voltage Alarm Enable
0: Disable
1: Enable
If this parameter is set to 0, the
P71 parameter will not be
displayed.
1
P71 High Voltage Alarm Limit 200 ... 650 V 445
P72 Phase Order Check Enable
0: Disable
1: Enable
1