Figure 18.1 Display unit translation
Figure 18.2 Parameter list translation
NOTE #### signifies the live value
18.3 Test procedure for transducer signals
It is essential to test the transducer signals into the DEIF controller. Please follow these steps to verify the good functionality. All 4-20
mA inputs may be used. In the example, the mains power transducer is used (multi-configurable input 102).
Terminal
Designation
102 Not used
103 + (4 to 20 mA)
104 0 (common)
COMMISSIONING GUIDELINES 4189341077D EN Page 55 of 58