4.2.1 Power management CAN bus
These menus are used if the ASC is part of an integrated system (power management system). The menus are not used if the ASC
is the only controller in a stand-alone system.
Terminal Function Associated menus
A1 Power management communication CAN H
7841, CANport select
7870, actions at CAN failure
A3 Power management communication CAN L
Notice that the CAN bus line has to be terminated in each end with a 120 Ω resistor. The recommended CAN bus cable is a Belden
3105A or Lapp CAN bus cable or an equivalent cable.
COMMISSIONING GUIDELINES 4189341077D EN Page 14 of 58