What should I do if the engine runs, but the Deif Controller shows genset to be OFF?
A
Aaron CampbellSep 2, 2025
If the engine runs, but the Deif Controller shows the genset to be OFF, check if the alternator voltage signal (L1 phase) is received by the controller terminal. Also, check if the LOP and LLOP are working OK, and verify the wiring to the controller.
M
Mr. Phillip BridgesSep 15, 2025
What does it mean when Deif SGC 420 shows Error C03?
D
David StewartSep 15, 2025
Error C03 on the Deif Controller can occur if the controller is disconnected from the PC during a configuration. To resolve this:
1. Push and hold the Stop/Config button during a power cycle to reset the controller.
2. Re-send the configuration file.
M
mejiakeithAug 31, 2025
How to resolve Error C03 on Deif SGC 420?
Z
zmorganAug 31, 2025
Error C03 on the Deif Controller can occur if the controller is disconnected from the PC during a configuration. To resolve this:
1. Press and hold the Stop/Config button during a power cycle to reset the controller.
2. Re-send the configuration file.
C
Chad WellsSep 18, 2025
What to do if Deif Controller shows incorrect reading for any of LOP, fuel level or engine temperature sensors?
G
Gary ShawSep 18, 2025
If the Deif Controller shows an incorrect reading for any of LOP, fuel level, or engine temperature sensors:
* Check respective sensor and its wiring.
* Check the SCP wiring.
* Go to the Configuration menu on the controller. Make sure the failing sensor is calibrated and configured correctly.
A
aonealSep 17, 2025
What to do if Deif Controller display is not responding?
V
vwilliamsSep 17, 2025
If the Deif Controller display is not responding, reset the controller power.
T
Tony McdanielSep 23, 2025
Why the engine runs, but the Deif Controller shows genset to be OFF?
C
Christine BrownSep 23, 2025
If the engine runs, but the Deif Controller shows genset to be OFF:
* Check the alternator voltage signal (L1 phase) is received by the controller terminal.
* Check if the LOP and LLOP are working correctly. Check the wiring to the controller.
N
Nicole NicholsonAug 28, 2025
What to do if Deif Controller does not power ON?
J
juarezcarlosAug 28, 2025
If the Deif Controller does not power on, check the battery voltage, the fuse on the battery supply, the continuity between battery positive and controller terminal 2, and the continuity between battery ground and controller terminal 1.
D
david99Aug 27, 2025
What to do if Deif SGC 420 Controller shows emergency stop alarm without emergency stop activated?
J
Jenny WoodAug 27, 2025
If the Deif Controller shows an emergency stop alarm without the emergency stop being activated:
* Check if the Emergency stop switch is working correctly, including the wiring.
* Enter the Configuration mode in the controller and verify the configuration of the Emergency stop polarity.
J
joshua77Aug 26, 2025
What to do if Deif SGC 420 Controller generates unnecessary shutdown alarms or warning alarms?
W
Walter LewisAug 26, 2025
If the Deif Controller generates unnecessary shutdown or warning alarms, take these actions:
* Check the respective switch, sensor and wiring.
* Go to the Configuration menu. Make sure the threshold values for the alarms and warnings are configured correctly.
A
adamsgeraldAug 25, 2025
What to do if Deif SGC 420 Controller shows Charging Alt Fail alarm?
A
Andrea RussellAug 26, 2025
If the Deif Controller displays a Charging Alt Fail alarm, here are some steps to investigate:
* To check if the controller's charging alternator terminal is working: Disconnect the charging alternator wiring to the controller's terminal 10. Short the terminal 10 to the ground through a DC ammeter. Crank-start the engine. The DC ammeter should indicate the current in the range of 200 to 400 mA for ~30 seconds. If yes, the controller's charging alternator terminal is working correctly.
* Disconnect and re-connect the charging alternator ind connection to the controller's terminal 10.
* Check if the charging alternator is working corrctly.