DEKA DURATION DD5300
24
ATTENTION:
Before stacking the batteries, the installer must check the maximum permissible floor load. It is recommended
that the installer obtains approval from a civil engineer.
For vertical ground mounting, the support surface of the Battery Module is distributed on 4 insulated supports
(rubber pads), 10 x 4 cm each. Make sure to install a distribution plate or make a proper foundation to support the
weight.
In case of horizontal installation, the installer must prepare an adequate distribution plate on the floor in order to
make a safe and stable support for the battery stack.
ATTENTION:
Ensure the support and/or the floor surface is adequate to support the battery load.
Do not stack more than eight modules.
`
631.5 lb (286.5 kg)
505.2 lb (229.2 kg)
378.9 lb (171.9 kg)
252.6 lb (114.6 kg)
11 126.3 lb (57.3 kg)
lb (kg)